OM-303 Page 14

5-4. Electrical Service Guide

S-0092J

.

For 230 V models with wall receptacle, 100% duty cycle used to calculate data below. 20% duty cycle used for all other models.

Input Voltage

200

230

380

415

460

Input Amperes At Rated Output

60

52

39

36

33

Max Recommended Standard Fuse Rating In Amperes

1

Time-Delay

2

70

60

45

40

30

Normal Operating

3

90

80

60

50

40

Min Input Conductor Size In AWG

4

10

6

12

12

14

Max Recommended Input Conductor Length In Feet (Meters)

42

(13)

135

(41)

151 (46)

181 (55)

85 (26)

Min Grounding Conductor Size In AWG

4

10

8

12

12

14

Reference: 2005 National Electrical Code (NEC) (including article 630)

1 Consult factory for circuit breaker applications.
2 “Time-Delay” fuses are UL class “RK5” .

3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).

4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table

310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

5-5. Connecting Input Power

ST-161 454-A

Tools Needed:

Y Have only qualified persons

make this installation.

Y Disconnect and lockout/tagout

input power before connecting

input conductors for wall recep-

tacle or from unit.

Y Special installation may be

required where gasoline or vola-

tile liquids are present − see NEC

Article 511 or CEC Section 20.

230 Volt Models:
Units come equipped with input power

cord and plug. Wall receptacle is cus-

tomer supplied. To install, select type

and size input and grounding conduc-

tors using Section 5-4. Conductor rating

must comply with national, state, and

local electrical codes.
Install and connect grounding conduc-

tor and input conductors in conduit or

equivalent between wall receptacle and

deenergized line disconnect device.
All Other Models:
Units come equipped with input power

cord for installation into line disconnect

device. Select type and size overcur-

rent protection using Section 5-4.

All Other

Models

230 Volt

Models Only

230 VAC, 1

GND/PE

L1

GND/PE

L2

L1

L2

When making connections in the line

disconnect device, connect the Green

Or Green/Yellow ground conductor first.

Install conductors into a

deenergized line disconnect

device.