The MK-Manta I Core Drill rig has been equipped with either a 20 Amp/115V 3

speed motor, a 20 Amp/120V 2 speed motor, or a 15 Amp/115V 2 speed motor.

The drill should be used on an electrical circuit, separate from other loads, and

protected by a 30 amp circuit breaker.

The MK-Manta I has been provided with a 20 Amp plug (NEMA 15-20) or a 30

Amp (NEMA 15-30) locking plug depending on the model.

The MK Manta is marked “Grounding Required” and has a three wire cord and

three prong grounding plug. The plug must be connected to a properly grounded

outlet (see figure below). If the tool should electrically malfunction or break

down, grounding provides a low resistance path to carry electricity away from

the user, reducing the risk of electrical shock.

The grounding prong in the plug is connected through the green wire inside the

cord to the grounding system in the tool. The green wire in the cord must be the

only wire connected to the tool’s grounding systems and must never be attached

to an electrically live terminal.

Your tool must be plugged into an appropriate outlet, properly installed and

grounded in accordance with all codes and ordinances. The plug and outlet

should look like those in the figure to the left.

Improperly connecting the grounding wire can result in the risk of electric shock.

Check with a qualified electrician if you are in doubt as to whether the outlet

is properly grounded. Do not modify the plug provided with the tool. Never

remove the grounding prong from the plug. Do not use the tool if the cord or

plug is damaged. If damaged, have it repaired by an authorized service facility

before use. If the plug will not fit the outlet, have a proper outlet installed by a

qualified electrician. The use of a circuit protected by a ground fault interrupter

(GFI) is highly recommended.

Use extension cords of the proper cable size, referring to the following chart.

Cord Length

25 feet

50 feet

75 feet

Wire Size (AWG)

#10

#8

#6

Never use an extension cord smaller than shown in the chart. Be sure your

extension cord is properly wired and in good electrical condition. Always replace

a damaged extension cord or have it repaired by a qualified electrician before

using it.

Protect your extension cords form sharp objects, excessive heat and damp or

wet areas.

Notice:

Using an extension cord with inadequately sized wire causes a serious

drop in voltage, resulting in loss of power and possible tool damage.

NEMA L5-20 125 V, 20 Amp

Locking Plug and receptacle

Grounding

blade

Cover of grounded outlet

box

Extension Cords

Drilling Operations

Electrical Requirements

Grounding

Э

Э

NEMA L5-30 125 V, 30 Amp

Locking Plug and receptacle

Grounding

blade

Cover of grounded outlet

box

Э

Э

WARNING

!

WARNING

!