Vermont castings ewf36a, Install top housing or termination, Installing chimney in a chase – Majestic Appliances EWF36A User Manual

Page 14: Finishing, Finish wall

Advertising
background image

14

Vermont Castings EWF36A

20005167

There must be a 2” (51mm) air space between outer-
most portion of chimney sections and any adjacent
combustible surfaces. (Combustible surfaces include
burnable materials such as: ceiling members, joists,
flooring, combustible insulation and roof structures.)

WARNING: Do not pack required air spaces with
insulation or other materials.

Mark an outline of the roof hole around the center of the
point nail. NOTE: Hole dimensions given in the chim-
ney top installation instructions are horizontal dimen-
sions; therefore, the hole size must be marked on the
roof accordingly.

Cover the opening of the installed chimney so debris
cannot get into the system.

Cut and frame the hole. It is good practice to use
framing lumber that is the same size as the rafters.
Install the frame securely because the chimney top and
flashing anchored to the frame must be able to with-
stand heavy winds.

Install Remainder of Chimney Sections

Since you have already preplanned the height of your
termination according to the

Ten Foot Rule, continue to

install pipe to the predetermined height.

Check the chimney top installation instructions for
details on how high above the roof top the chimney
sections (all pipes) should extend.

Install Top Housing or Termination

Follow the installation instructions provided with the
Vermont Castings, Majestic Products chimney termina-
tion you have selected.

Installing Chimney in a Chase

Refer to Figure 2, Page 5 for an illustration of a typical
chase installation.

CAUTION: Treatment of firestop spacers and construc-
tion of chase may vary with type of building. These
instructions are not a substitute for local building codes.
You must check your local building codes to determine
specific requirements for your city or state. NOTE:
Other building materials may be required in addition to
Vermont Castings, Majestic Products Firestop Spacers.

Finishing

CAUTION: All joints between the finished wall and the
fireplace surround (steel front) must be sealed with
noncombustible material to prevent cold air leakage into
the room. (Fig. 19)

NOTE: No material may cover black cast face.

Finish Wall

Finish the wall with material of your choice. Do not
install a combustible mantel shelf less than 12”
(305mm) above the firebox grille opening. Do not
install a mantel face plate less than 6” (159mm)
from top of grille opening. (Fig. 21)
If a combustible
material is used below a flat mantel shelf, consult your
local building codes for minimum clearance from top of
fireplace opening to bottom of mantel shelf.

All joints (top, bottom and sides) where wall or decora-
tive facing material meets fireplace surround must be
completely sealed with a noncombustible material.
(Figures 20 and 24)

NOTE: No side wall protection is required for fireplaces
installed at 45

°

to two (2) side walls (corner installation).

Air Space Clearances

Combustible framing material MUST NOT
penetrate AIR SPACE (shaded areas)

Standoff

2”

(51mm)

Firestop

1” (25mm)
Space to Back

1” (25mm)
Air Space
to Sides

Wall
Shield

0” Clearance
to Floor

Hearth Extension

FP1199

Fig. 19 Minimum clearances to combustibles.

1” (25mm) Air

Space to Sides

NO
material
may cover
cast face