Options:

- 1 45 deg concentric elbow

- 2 90 deg concentric elbow

- 1 concentric extension

- 1 straight horizontal flue kit

  &21'(16$7( '5$,1 &211(&7,21

Connection of the condensate drain piping system
is to the back of the unit beneath the flue/combus-
tion air separator tube assembly. The condensate
drain tube provided in the unit is 1 - 19/32 inches (40
mm) O.D. to which the drain trap assembly supplied
with the unit may be connected. The condensate
drain outlet connection on the trap is 1 - 19/32 in-
ches (40mm) O.D. to which standard 1 -1/2 inch tra-
de size schedule 40 PVC pipe can be connected to
create the rest of the drain system. The drain sys-
tem must pitch downward towards the sewer.

Note: The condensate will not likely require any spe-
cific water treatment because of condensate dilution
by normal wastewater use. If, however, local regula-
tions require wastewater to have a neutral pH, a
condensate treatment tank can be installed
between the trap and the sewer.

1,

80

m

5.

9

f

t

1 in

rear boiler

view from above

45° elbow

90° elbow

5

6

7

8