Majestic fireplaces, Br/bc series, Side wall protection – Majestic Appliances BC42 User Manual

Page 16: Hearth installation, Minimum wall clearances, Minimum hearth extension dimensions

Advertising
background image

16

Majestic Fireplaces

®

BR/BC Series

7412944

Side Wall Protection

Adjacent combustible side walls that are within mini-
mum dimensions shown in Figure 23 of the fireplace
opening must be protected with CFM Corporation Wall
Shield Model SP40 or a specifically built wall shield
described in Figure 20.
The special wall shield design described in Figure 20 is
an alternate method of adding protection to side walls
and can be used in place of the SP40 with the same
wall clearances specified for the SP40. Rt must =1.85
minimum.
Examples of wall shield insulation:

1. Manville - CERAFORM 126, K=.27,
1/2 inches thick
2. CFM Corporation - EH2416, K = .458,
1 inch thick required.

Hearth Installation

A hearth extension is required to protect a combustible
floor in front of the fireplace. Refer to Figure 23 for mini-
mum dimensions and mounting detail.
NOTE: Hearth Extension must not cover the air
inlet opening of a fireplace.
The hearth extension described in Figure 23 must be a
durable noncombustible material with a minimum (total)
Rt value of 1.09; see Figure 24 for examples. The over-
all height (above a combustible floor), depth and width
must be as indicated, with the extension centered to the
fireplace opening.
The top of insulation must be covered with a noncom-
bustible decorative covering or a piece of .018” mini-
mum sheet metal, to protect hearth extension material.
(Fig. 23)
Secure the hearth extension to the floor to prevent
shifting, using trim molding or other similar means at
three (3) outer edges. Seal crack between the fireplace
hearth and hearth extension with a noncombustible
material. (Figs. 23 and 25)

Minimum Wall Clearances

WITH

Noncombustible

Surround Facing

WITHOUT

Noncombustible

Surround Facing

Minimum Hearth Extension Dimensions

(for On-Site Construction)

G

H

G

J

Seal cracks

between the

fireplace

and hearth

extension with

noncombustible

material

Safety strips

must overlap

���

" minimum

May install

noncombustible

decorative

covering

OR .018" min.

sheet metal

Fireplace

Hearth

Combustible

Floor

Minimum

Insulation

Value "R"

4" MIN.

FP594
SR/SC
11/20/97

Firebox

Opening

A - Min. clearance

to combustible

perpendicular wall

B - Min. clearance

to combustible

perpendicular wall when

using noncombustible wall shield*

Side

Wall

Side

Wall

F**

C**

E

E

D

4" Brick

(Example material)

Combustible material permitted within shaded area.

* Noncombustible wall shield requires 1" CFM Corporation

EH2416 insulation (minimum R Value = 1.85) between

decorative noncombustible rigid covering and combustible wall.

Minimum height and width is 40" x 40".
** Dimension/degree of angle will vary depending on thickness

of noncombustible surround facing.

4"

Shaded area starts

1/2" away from

edge of unit

FP594

Fig. 23 Combustible side wall protection and hearth extension dimensions.

A

B

C

D

E

F

G

H

J

BR/BC36

16"

12"

48°

41°

18"

14"

9"

16"

48"

406 mm 305 mm

457 mm 356 mm 229 mm 406 mm 1219 mm

BR/BC42

20"

12"

42°

35°

18"

14"

12"

20"

61¹⁄₂"

508 mm 305 mm

457 mm 356 mm 305 mm 508 mm 1562 mm