Majestic fireplaces, Br/bc series, Chimney requirements - offset installations – Majestic Appliances BC42 User Manual

Page 6: 30˚ elbow offsets, Illustration key

Advertising
background image

6

Majestic Fireplaces

®

BR/BC Series

7412944

Chimney

Support

Chimney Requirements - Offset Installations

0 0 0 0 0

3"

11"

1 0 0 0 0

8¹⁄₄"

20"

0 1 0 0 0 11¹⁄₄" 25¹⁄₄"
2 0 0 0 0 13¹⁄₂" 29¹⁄₄"
1 1 0 0 0 16¹⁄₂" 34¹⁄₄"
0 0 1 0 0 20¹⁄₄" 40³⁄₄"
2 1 0 0 0 21³⁄₄" 43¹⁄₂"
0 0 0 1 0 26¹⁄₄" 51¹⁄₄"
0 1 1 0 0 28¹⁄₂" 55¹⁄₄"
1 0 0 1 0 31¹⁄₂" 60¹⁄₄”
0 1 0 1 0 34¹⁄₂" 65¹⁄₂"
0 0 2 0 0 37¹⁄₂" 70³⁄₄"
1 1 0 1 1 41¹⁄₂" 77³⁄₄"
0 0 1 1 1

45" 83³⁄₄"

0 1 2 0 1 47¹⁄₄" 87¹⁄₂"
0 0 0 2 1

51"

94"

0 1 1 1 1 53¹⁄₄"

98"

0 0 3 0 1 56¹⁄₄" 103¹⁄₄"
0 1 0 2 1 59¹⁄₄" 108¹⁄₂"
0 0 2 1 1 62¹⁄₄" 113¹⁄₂"
0 1 3 0 1 64¹⁄₂" 117¹⁄₂"
0 0 1 2 1 68¹⁄₄"

124"

0 1 2 1 1 70¹⁄₂"

128"

0 0 0 3 1 74¹⁄₄" 134¹⁄₂"
0 1 1 2 2

78" 140³⁄₄"

0 0 3 1 2

81"

146"

0 1 0 3 2

84" 151¹⁄₄"

0 0 2 2 2

87" 156¹⁄₂"

0 1 3 1 2 89¹⁄₄" 160¹⁄₄"
0 0 1 3 2

93" 166³⁄₄"

0 1 2 2 2 95¹⁄₄" 170³⁄₄"
0 0 0 4 2 99¹⁄₄" 177³⁄₄"
0 1 1 3 2 101¹⁄₄" 181³⁄₄"
0 0 3 2 2 104¹⁄₄" 186¹⁄₄"
0 1 0 4 2 107¹⁄₄" 191¹⁄₂"
0 0 2 3 2 110¹⁄₄" 196³⁄₄"
0 1 3 2 3 114" 203¹⁄₄"
0 0 1 4 3 117³⁄₄" 209³⁄₄"
0 1 2 3 3 120" 213¹⁄₂"
0 0 0 5 3 123³⁄₄"

220"

30˚ Elbow Offsets

1' 1¹⁄₂' 3' 4'

Offset

Rise

Notes: G + H cannot exceed 20 feet.

Air Space Clearances: SK8 (2-wall) = 1¹⁄₂" and "S" Series (3-wall) = 2"

Illustration Key

The following safety rules apply to
offset installations (letters correspond
with illustration above):
A. Height of the chimney is measured
from the hearth to the chimney exit.

BR/BC36 BR/BC42

Maximum:

90'0"

90'0"

Minimum:
Without Elbows 12' 6"

12' 6"

With 2 Elbows* 14' 6"

14' 6"

With 4 Elbows* 21' 0"

21' 0"

B. Do not use more than 4 elbows per
chimney.
Attach the straps of the return (top)
elbow to a structural framing member.
The offset (first) elbow of any pair does
not have straps.

FP269

C. The chimney cannot be more than 30˚
(45˚ in Canada) from the vertical plane in
any installation*.
D. The maximum length of the angled run
of the total chimney system is 20 feet. (G
plus H cannot exceed 20 feet.)
E. A chimney support (Model SKCS8)
is required every 6 feet of angled run of
chimney. Chimney supports are required
for every 30 feet and 60 feet (SK8 pipe)
or 20 feet and 40 feet (3-wall pipe) of ver-
tical chimney height above the hearth.
Determine the offset distance of your
chimney arrangement from the centerline
of the fireplace to the centerline of the
chimney where it is to pass through the
first ceiling.

NOTE: This offset distance may not be
your full offset distance. See Examples 2
and 3.

FP282

MBUF

5/26/96

OFFSET

RISE

FP282

* In Canada, two (2) SK845 are allowed.

Fig. 6. Chimney system requirements.

D

RISE

B

G

H

B

OFFSET

C

E

6 FT.

G

H

A

HEARTH

FLOOR

CHIMNEY

SECTION

CHIMNEY FLUE EXIT

ELBOW

FP269
MBUF

5/16/96

rev. 5/25

30˚

OFFSET

ELBOW

30˚

OFFSET

ELBOW

30˚

RETURN

ELBOW

30˚

RETURN

ELBOW

SKCS8

SUPPORT

Example 1

Example 2

Example 3