9-8. Overload Protection

802 170-D / Ref. 802 311

2

1

9

8

7

4

Y Stop engine.

.

When a circuit breaker or fuse
opens, it usually indicates a

more serious problem exists.

Contact Factory Authorized

Service Agent.

1

Fuse F1

2

Fuse F2

F1 and F2 protect the stator exciter

winding from overload. If F1 opens,

weld and generator power is low or

stops entirely. If F2 opens, weld out-

put is low or stops entirely. 4 kVA/kW

generator power is still available.
3

Circuit Breaker CB4 (Not

Shown)

4

Circuit Breaker CB5

(CC/CV Models Only)

5

Circuit Breaker CB6

(CC/CV Models Only)

6

Circuit Breaker CB10 (Not

Shown)

7

Circuit Breaker CB11

8

Circuit Breaker CB12

9

Circuit Breaker CB13

CB4 protects the welding arc drive

(dig) circuit. If CB4 opens, electrode

may stick to the workpiece more fre-

quently during low voltage (short arc

length) conditions. CB4 automatical-

ly resets when the fault is corrected.
CB5 protects the 24 volt ac output to

remote receptacle RC14, and 24 volt

output to field current regulator board

PC1 (CC/CV models only). If CB5

opens, weld output and 24 volt out-

put to RC14 stops. On units with op-

tional three−phase generator, gener-

ator power output at receptacle RC5

also stops if CB5 opens.
CB6 protects the 115 volt ac output

to remote receptacle RC14 (CC/CV

models only). If CB6 opens, 115 volt

output to RC14 stops.
CB10 protects the engine battery cir-

cuit. If CB10 opens, the engine will

not crank. CB10 automatically re-

sets when the fault is corrected.
CB11 protects the engine wiring har-

ness. On CC models, if CB11 opens

the max OCV circuit does not work

and open circuit voltage is variable at

all times (see max OCV note under

Weld Controls in Section 6-2). If

CB11 opens on CV models, weld

output stops (generator power is still

available).
CB12 protects the field flashing cir-

cuit. If CB12 opens, the generator

may not excite at start-up and weld

and generator power output may not

be available.
CB13 protects the engine shutdown

circuit. If CB13 opens, the engine

cranks but does not start.
Press button to reset breaker.