Micro Technic Micronix PV-5127 User Manual

Page 21

Advertising
background image

Users Manual & Installation Guide

PV- 5127:

Power supply module with UPS

Page 21 of 31

mounted directly on the battery. The charging is disabled when the temperature according to this

sensor rises above 55°C, and enabled when it falls below 45°C. The J1 input has the following

function:

Installed on J1

Charger function

Nothing

Disabled. See note.

A jumper

Enabled (factory default)

A KTY11-5 sensor

Enabled when not too hot

Note: When using the PV-5127 with a PV-1075 NiMH battery module, you must disable the PV-

5127 charger by leaving J1 unconnected.

You can connect a Battery LED to the CN2 connector. The LED shows these statuses:

Battery LED Meaning

Off

Battery voltage OK (

medium

or

full

). If mains is present and the charger is enabled,

the charger is in

trickle charge

mode, otherwise it is

off

.

Flashing

Charger is in

fast charge

mode.

Steady on

Battery error. This indicates that the battery is either

empty

,

low

, or

disconnected

.

) 6

)

#)

7

89"

7

. )

)

6

7 - *

. )

)

=

)

7(

#)

7
7

#)

<

=

)

. )

)

6

7 - *

>

>

)

)

:).

)

?

)

?

)

:).

)