Intel Entry Redundant Power 2U ERP2U User Manual

Page 17

Advertising
background image

SSI

ERP2U Power Supply Design Guide, V1.0

- 17 -

6.4.1

Standby Outputs

STATUS

Required

The 5 VSB output shall be present when an AC input greater than the power supply turn on voltage is applied.

6.5 Voltage Regulation

STATUS

Required

The power assembly output voltages must stay within the following voltage limits when operating at steady state
and dynamic loading conditions. These limits include the peak-peak ripple/noise specified in Section 5.9. All
outputs are measured with reference to the return remote sense (ReturnS) signal. The 5 V, 12V1, 12V2, 12V3, –
12 V and 5 VSB outputs are measured at the power assembly connectors referenced to ReturnS. The +3.3 V is
measured at its remote sense signal (3.3VS) located at the signal connector.

Table 13: Voltage Regulation Limits

Parameter

MIN

NOM

MAX

Units

Tolerance

+3.3 V (optional)

+3.20

+3.30

+3.46

V

rms

+5/-3%

+5 V (optional)

+4.80

+5.00

+5.25

V

rms

+5/-4%

+12V1

+11.52

+12.00

+12.60

V

rms

+5/-4%

+12V2

+11.52

+12.00

+12.60

V

rms

+5/-4%

+12V3 (optional)

+11.52

+12.00

+12.60

V

rms

+5/-4%

-12 V

-11.40

-12.20

-13.08

V

rms

+9/-5%

+5 VSB

+4.85

+5.00

+5.25

V

rms

+5/-3%

STATUS

Optional

Some system applications may require tighter regulation limits on the +5 V output. The optional regulation limits
are shown below.

Table 14: Optional +5V Regulation Limits

Parameter

MIN

NOM

MAX

Units

Tolerance

+5 V

+4.85

+5.00

+5.25

V

rms

+5/-3%