ICP DAS USA 8KE8 User Manual

Page 73

Advertising
background image

#AASiCj
Command

#AASiCj

Description Reads the analog input or counter/frequency module data from

specified slot and the specified channel in the I-8000 unit.
#AASiCj[CHK](cr)
#

A delimiter character

AA

A 2-character HEX module address for the
specified I-8000 unit, ranging from 01 to FFh

Si

The specified slot number. i = 0 to 3 (4 slots) or
i = 0 to 7 (8 slots)

Cj

specified channel number.
i-87013

Î j = 0 to 3

i-8017H

Î j = 0 to 7

i-87017

Î j = 0 to 7

i-87018

Î j = 0 to 7

i-8080

Î j = 0 to 7

[CHK]

The 2-character of Checksum

Syntax

(cr)

Carriage Return(0x0D) for denote the end of the
command

Valid Command

>(data)[chk](cr)

Invalid Command

?AA[CHK](cr)

Any syntax or communication error may receive no response.
>

A delimiter for valid command

?

A delimiter for invalid command

AA

A 2-character HEX module address

(data)

A return string from RTD input module in
engineering mode.

[CHK] A

2-character

checksum

(cr)

Carriage Return (0x0D) to denote the end of the
response

Command

#01S3C0

Response

>+2.1234(cr)

Example

Description

The data read from the analog data input module
in slot 3 and channel 0 of the I-8000 unit at address
01h is +2.1234.

Notes: i-87013

Î 4-Channel RTD Analog Input Module

i-8017H

Î Fast 8-Channel mV/V/mA Analog Input Module

i-87017

Î 8-Channel mV/V/mA Analog Input Module

i-87018

Î 8-Channel mV/V/mA and Thermocouple Analog Input

Module
i-8080

Î 8-Channel Counter/Frequency Module

8430/8830/8KE4/8KE8 User’s manual, Jan 2005, Version 1.0, 8MS-002-10 ----- 73