DC Power Supply Precautions

The following precautions must be observed when installing the chassis model with
an internal DC power supply.

1. Check nameplate ratings to ensure there is no overloading of supply circuits that

could affect over current protection and supply wiring.

2. In addition, the following must be observed:

a. Connect the equipment to a 36 to 56.7 V DC power source that is

electrically isolated from the alternating current source.

Nominal
Voltage

Minimum
Voltage

Maximum
Voltage

Transient
Voltage

48 36 56.7

75.0*

* 75.0-V transient with a duration of 10.0 ms with a rate of rise and fall of

10 V/ms. The equipment shall meet its operational specifications during
the transient.

b. Route input wiring to terminal block and secure in such a manner that it is

protected from damage and stress. Do not route wiring past sharp edges or
moving parts.

c. Incorporate a readily accessible disconnect device, with a 3mm minimum

contact gap in the fixed wiring.

d. Install only in Restricted Access Areas (dedicated Equipment Rooms,

Equipment closets or the like) in accordance with Articles 110-18, 110-26,
and 110-27 of the National Electric Code, ANSI/NFPA 70.

e. Provide a listed circuit breaker suitable for branch circuit protection of the

wiring and rated maximum 1A @ 48 V DC.

f.

For supply connections, use wires suitable for at least 75° C.