Ultra reliable gas atmospheric boilers

High, full and part load efficiencies -
meets Building Regulations 2006 (Part L2)

Auto ignition

Remote indication kit options

CXA/H natural gas or propane CXA P/H (40-100kW)

CXA/H is On/Off and CXS/H is High/Low operation

Model 40/H

50/H

60/H

70/H

80/H

90/H

100/H

110/H

120/H

Sections

3

4

4

5

5

6

6

7

7

Output (kW)

40

50

60

70

80

90

100

110

120

Height

1000

Width

600

Depth

750

882

882

1042

1042

1212

1212

1385

1385

Flow/Return Connections (BSP)

RC2

Gas Inlet (BSP)

RC

3

/

4

RC

3

/

4

RC

3

/

4

RC

3

/

4

RC

3

/

4

RC1

RC1

RC1

RC1

Flue Size (mm)

150

150

175

175

200

200

200

250

250

Maximum Working Pressure (bar)

6

Water Content (L)

22

30

30

37

37

45

45

53

53

Approx Dry Weight (kg)

210

265

265

330

330

395

395

490

490

Front (mm)

750

Back (mm)

0

0

0

150

150

300

300

300

300

Sides (mm) 50

50

50

50

50

100

100

100

100

General Data Concord CXA/H S/H (40 - 120)

Option Kits

Boiler

CXA/H

CXS/H

Volt free contacts, boiler run,
overheat & lockout

Down draft thermostat kit

Header kits (available from merchants)

Propane models

Boiler
Clearances

Concord CXA/H S/H

40 - 120kW