Robust cast aluminium heat exchanger

In-built commissioning and fault diagnostics

Low NOx emissions

Volt free contacts supplied as standard

Meets Building Regulations 2006 (Part L2)

Compact size - small footprint

Fully modulating operation down to 20% of output

Up to 107.5% nett efficiency (fully condensing)

Fits through standard doorways

xtra

80 - 560kW

General Data

xtra (80 - 560)

Model

80

120

160

200

240

280

320

400

480

560

Boiler output (condensing)

25.6 -

25.6 -

32.0 -

47.1 -

51.4 -

55.6 -

75.3 -

107.5 -

116.1 -

118.3 -

50/30˚C

82.2

123.4

164.5

207.8

249.4

290.9

329.0

415.6

498.8

581.8

Boiler output (non-condensing)

23.3 -

23.2 -

29.0 -

43.1 -

47.0 -

51.0 -

67.8 -

97.7 -

105.5 -

107.7 -

80/60˚C

77.4

116.0

154.8

195.4

234.5

273.6

311.6

390.8

469.0

547.2

Height

1150

Width

600

600

600

600

600

600

1200

1200

1200

1200

Depth

1024

1024

1024

1327

1327

1327

1004

1326

1326

1326

Flow connection (BSP)

R2”

R2”

R2”

R2”

R2”

R2”

80*

80*

80*

80*

Return connection (BSP)

R2”

R2”

R2”

R2”

R2”

R2”

80*

80*

80*

80*

Gas inlet connection (BSP)

R1”

R1”

R1”

R1”

R1”

R1”

R2*

R2*

R2*

R2*

Nominal flue size / concentric (mm)

150

150

150

200

200

200

200

250

250

250

Maximum working pressure (bar)

6

Water content (L)

11.0

14.3

17.5

18.4

24.0

27.2

35.0

36.8

48.0

54.4

Weight (kg)

132

150

168

198

215

233

336

396

430

466

Front (mm)

600

Back (mm)

700

700

700

700

700

700

1000

1000

1000

1000

Side (mm) 450 150 450 150 450 150 450 150 450 150 450 150

450

450

450

450

(LH)(RH) (LH)(RH) (LH)(RH) (LH)(RH) (LH)(RH) (LH)(RH)

*DN flange. Flow, return and gas connection sizes shown are for the optional header kit.
If header kit not used: Flow & Return connections are 2 x R2. Gas connection is 2 x R1.

Extended

Output

Range

Option Kits

Boiler

xtra

80 - 280

320 - 560

Modulating sequence control for

controlling multiple boiler installations

Programmable room thermostat

Tank sensor kit

n/a

BMS control kit (0-10V)

Standard

Boiler

xtra

80 - 280

320 - 560

Outside sensor kit

Room sensor kit

Sequencer DHW sensor kit

Control interface kit

Standard

Boiler