IBM AA-RWF3A-TE User Manual

Page 111

Advertising
background image

CAUTION:

If the SFP you does not have a bale, use a small implement, such as a

screwdriver, to press and release the trigger beneath the port. Non-baled

SFPs can be damaged by the removal process and are not recommended.

See

SAN Swtich optional kits

on page 33 for a list of supported SFPs.

5.

Repeat this procedure for the remaining ports, as required.

To install a replacement SFP:

1.

Make sure that the bale is in the unlocked position, and then place the SFP in the

correctly oriented position on the port. See

Figure 39

.

NOTE:

Each SFP includes a 10-pad gold-plated PCB-edge connector on the

bottom. The correct position to insert an SFP into the upper row of ports is

with the gold edge down. The correct position to insert an SFP into the

lower row of ports is with the gold edge up.

2.

Slide the SFP into the port until you feel it click into place, and then close the bale.

SAN Switch installation guide

111

Advertising