Installation and safety considerations

Install the switch using one of the following methods:

As a stand-alone unit on a flat surface. See

Installing the switch as a stand-alone

device

on page 40.

HP highly recommends mounting the switch in one of the following HP customized

racks:
• HP System/e Rack
• HP 10000 G2 Series Rack, HP 9000 Series Rack and HP 10000 Series Rack

See

Installing the switch using the SAN Switch Rack Mount Kit

on page 41 for detailed

instructions.

Electrical considerations

For successful installation and operation of the switch, ensure that the following electrical

requirements are met. For power supply information, see

SAN Switch technical

specifications

on page 131.

Primary AC input 100–240 VAC, 2.0 A, 47–63 Hz (switch autosenses input

voltage)

A correctly wired primary outlet, with a circuit protected by a circuit breaker and

grounded in accordance with local electrical codes

Adequate supply circuit, line fusing, and wire size, as specified by the electrical

rating on the switch nameplate

Environmental considerations

Before installing the switch:

To ensure adequate cooling, install the switch with the nonport side (which

contains the air intake vents) facing the cool-air aisle.

Verify that a minimum of 24 cubic ft/minute of airflow is available to the air

intake vents on the nonport side of the switch.

Verify that the ambient air temperature does not exceed 40 ºC (104 ºF) while

the switch is operating.