Balancing damper, Maximizing the unit’s performance, Balancing the unit – Imperial SHMTM User Manual

Page 11: Before starting the balancing operations

Advertising
background image

figure 11.3 Magnehelic Gauge at «0»

PAGE 11

STATIC AND STATIC WITH MOTORIZED DAMPERS MODELS

Maximizing the

unit’s

performance

installation

The HRV must be balanced properly in
order to operate at maximum performance
and avoid problems.

Balancing the Unit

installation

Balancing the unit is an important step in
the installation of the HRV. The operation
consists of measuring and regulating the
volume of fresh air from outside passing
through the unit is equal with the exhaust
air from home.

A 10% variation is acceptable, in such case,
the volume of exhaust air from home
should be superior than the volume of fresh
air from outside.

Refer to Ventilation Needs, page 3 to
determine what is the volume of air needed
for your specific installation.

Before Starting

the Balancing

Operations

installation

A Magnehelic gauge equiped with an air
flow grid is used to measure the volume of
air passing through the unit and ducting sys-
tem. Make sure that the airflow grid is the
same size as the conduit beeing mesured.
Check for size on grid. (Figure 11.6)

11. Balancing Damper

Step 1: To get proper readings, mount the air flow
grid inside a rigid ducting at a minimum of 18 inches
from the unit. This will avoid getting unstable airflow
witch could offset the readings. (Figure 11.2)

Step 2: Start with the fresh air from outside duct.
Drill a hole in the conduit and insert the air flow grid.
Make sure to mount the grid following the direction of
the airflow arrow. (Figure 11.3)

Step 3: The magnehelic gauge needs to be leveled
and should read «0» before taking any readings.
Determine your airflow volume by consulting the grid’s
chart. It can differ from one gauge size to an other.
(Figure 11.4)

Step 4: On this unit the airflow is regulated by a
balancing damper installed inside the ISF

TM

collar system

located on the top right side of the HRV. (Figure 11.1)

Measure and regulate the «fresh air from outside»
damper until desired airflow volume. Repeat the same
steps for the «exhaust air from home» damper.

Step 5: Finish the balancing operation by tapping
all the holes made from the mounting of the airflow
grid. (Figure 11.5)

figure 11.1 Balancing Dampers- Model SHM

TM

and Model SH

TM

figure 11.6 Magnehelic Gauge with Air Flow

Grid

figure 11.2 Minimum of 18”

figure 11.3 Inserting Air flow grid in duct

figure 11.5 Avoid leakage by sealing air flow

grid in duct with duct tape.

18”

Balancing Dampers