Install the I/O Shield

NOTE

An ATX 2.03-compliant I/O shield should be provided with your server
board. The shield is required by Electromagnetic Interference (EMI)
regulations. It minimizes EMI and ensures proper cooling of the server.

The shield fits the rectangular opening near the power supply in the back of the chassis. The shield
has cutouts that match the external I/O connectors (e.g., keyboard and mouse).

1. If an EMI gasket was provided with your server board, install it now.
2. Install the shield from the inside of the chassis. Orient the shield so that the cutouts align with

the corresponding I/O connectors on the server board.

3. Position one edge of the shield so that the dotted groove is outside the chassis wall and the lip

of the shield rests on the inner chassis wall.

4. Hold the shield in place, and push it firmly into the opening until it is seated. Make sure the

I/O shield snaps into place all the way around.

TP00074

Figure 5. Installing the I/O Shield