Johnson Controls R-410A User Manual

Page 43

Advertising
background image

333496-BTG-E-0610

Johnson Controls Unitary Products

43

042

(3.5)

1400

55

MBH

12.22

14.83

18.06

22.05

27.01

33.13

40.72

50.11

KW

1.12

1.33

1.55

1.76

1.98

2.19

2.41

2.62

70

MBH

10.97

13.58

16.81

20.81

25.76

31.89

39.47

48.87

KW

1.90

2.11

2.33

2.54

2.76

2.97

3.19

3.40

80

MBH

10.65

13.26

16.49

20.49

25.44

31.57

39.16

48.55

KW

1.98

2.19

2.41

2.62

2.84

3.05

3.27

3.48

1500

55

MBH

12.89

15.51

18.75

22.77

27.75

33.93

41.58

51.06

KW

1.46

1.64

1.83

2.04

2.27

2.52

2.79

3.09

70

MBH

10.94

13.56

16.80

20.82

25.80

31.98

39.63

49.11

KW

1.98

2.16

2.35

2.56

2.79

3.04

3.31

3.60

80

MBH

10.47

13.09

16.33

20.35

25.34

31.51

39.16

48.64

KW

2.66

2.84

3.03

3.24

3.47

3.72

3.99

4.28

1600

55

MBH

11.68

14.30

17.55

21.57

26.55

32.72

40.37

49.84

KW

1.37

1.51

1.65

1.80

1.97

2.14

2.32

2.52

70

MBH

10.98

13.60

16.85

20.87

25.85

32.02

39.67

49.14

KW

2.17

2.31

2.45

2.60

2.77

2.94

3.12

3.32

80

MBH

10.48

13.10

16.35

20.37

25.35

31.52

39.17

48.64

KW

2.27

2.41

2.55

2.70

2.87

3.04

3.22

3.42

048

(4.0)

1600

55

MBH

14.54

17.52

21.19

25.70

31.24

38.07

46.47

56.81

KW

1.44

1.68

1.93

2.17

2.42

2.66

2.91

3.15

70

MBH

12.93

15.91

19.57

24.08

29.63

36.46

44.86

55.19

KW

2.13

2.37

2.62

2.86

3.11

3.35

3.60

3.84

80

MBH

11.83

14.81

18.47

22.98

28.53

35.36

43.76

54.09

KW

2.69

2.93

3.18

3.42

3.67

3.91

4.16

4.40

1800

55

MBH

13.73

16.74

20.46

25.05

30.71

37.70

46.32

56.95

KW

1.80

1.97

2.14

2.34

2.54

2.76

3.00

3.25

70

MBH

12.89

15.90

19.62

24.21

29.87

36.86

45.48

56.11

KW

2.30

2.47

2.64

2.84

3.04

3.26

3.50

3.75

80

MBH

12.19

15.20

18.92

23.51

29.17

36.16

44.78

55.41

KW

2.70

2.87

3.04

3.24

3.44

3.66

3.90

4.15

060

(5.0)

1800

55

MBH

20.43

23.92

28.12

33.17

39.24

46.53

55.30

65.83

KW

2.33

2.46

2.60

2.75

2.90

3.07

3.24

3.41

70

MBH

17.33

20.82

25.02

30.07

36.14

43.43

52.20

62.73

KW

2.93

3.06

3.20

3.35

3.50

3.67

3.84

4.01

80

MBH

15.53

19.02

23.22

28.27

34.34

41.63

50.40

60.93

KW

3.37

3.50

3.64

3.79

3.94

4.11

4.28

4.45

2000

55

MBH

20.02

23.56

27.83

32.99

39.22

46.74

55.83

66.81

KW

2.44

2.56

2.68

2.81

2.94

3.08

3.22

3.37

70

MBH

17.02

20.56

24.83

29.99

36.22

43.74

52.83

63.81

KW

2.97

3.09

3.21

3.34

3.47

3.61

3.75

3.90

80

MBH

15.22

18.76

23.03

28.19

34.42

41.94

51.03

62.01

KW

3.47

3.59

3.71

3.84

3.97

4.11

4.25

4.40

1. These Capacities are net capacities - the indoor motor heat has been added.
2. These power inputs are total power inputs - the indoor motor watts have been added.

BUQ024-060 (Continued)

Size

(Tons)

Air Over Evaporator

Coil

Capacity

1

& kW

2

Outdoor Temperature (°F @ 72% RH)

CFM

DB (°F

)

-10

0

10

20

30

40

50

60

Advertising