Electric heat minimum supply air, Indoor blower specifications, Electric heat multipliers – Johnson Controls R-410A User Manual

Page 58

Advertising
background image

333496-BTG-E-0610

58

Johnson Controls Unitary Products

Electric Heat Minimum Supply Air

Size

(Tons)

Model

Voltage

Minimum Supply Air (CFM)

Heater kW

3.8/5.0

5.6/7.5

7.5/10.0

11.3/15.0 15.0/20.0 18.8/25.0

024

(2.0)

BUZ

208/230-1-60

800

800

800

-

-

-

BUX

BUQ

208/230-1-60

720

720

720

-

-

-

030

(2.5)

BUZ

BUQ

208/230-1-60

1000

1000

1000

1000

-

-

208/230-3-60

1000

1000

1000

1000

-

-

460-3-60

1000

1000

1000

1000

-

-

036

(3.0)

BUZ

208/230-1-60

1200

1200

1200

1200

-

-

208/230-3-60

1200

1200

1200

1200

-

-

460-3-60

1200

1200

1200

1200

-

-

BUX

BUQ

208/230-1-60

1080

1080

1080

1080

-

-

208/230-3-60

1080

1080

1080

1080

-

-

460-3-60

1080

1080

1080

1080

-

-

042

(3.5)

BUZ

208/230-1-60

-

-

1225

1225

-

-

208/230-3-60

-

-

1225

1225

-

-

460-3-60

-

-

1225

1225

-

-

BUQ

208/230-1-60

-

-

1400

1400

-

-

208/230-3-60

-

-

1400

1400

-

-

460-3-60

-

-

1400

1400

-

-

048

(4.0)

BUZ

208/230-1-60

-

-

1600

1600

1600

1600

208/230-3-60

-

-

1600

1600

1600

1600

460-3-60

-

-

1600

1600

1600

1600

BUX

BUQ

208/230-1-60

-

-

1440

1440

1440

1440

208/230-3-60

-

-

1440

1440

1440

1440

460-3-60

-

-

1440

1440

1440

1440

060

(5.0)

BUZ

208/230-1-60

-

-

1750

1750

1750

1750

208/230-3-60

-

-

1750

1750

1750

1750

460-3-60

-

-

1750

1750

1750

1750

BUX

BUQ

208/230-1-60

-

-

1900

1900

1900

1900

208/230-3-60

-

-

1900

1900

1900

1900

460-3-60

-

-

1900

1900

1900

1900

Indoor Blower Specifications

Size

(Tons)

Model

Motor

HP

RPM

Eff.

SF

Frame

024

(2.0)

BUZ
BUX

BUQ

1/2

Variable

0.8

1.0

48

030

(2.5)

BUZ

BUQ

1/2

Variable

0.8

1.0

48

036

(3.0)

BUZ
BUX

BUQ

3/4

Variable

0.8

1.0

48

042

(3.5)

BUZ

BUQ

3/4

Variable

0.8

1.0

48

048

(4.0)

BUZ
BUX

BUQ

3/4

Variable

0.8

1.0

48

060

(5.0)

BUZ
BUX

BUQ

1

Variable

0.8

1.0

48

Electric Heat Multipliers

Voltage

kW Capacity Multipliers

1

1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat

capacity for heaters applied at lower voltages.

Nominal

Applied

240

208

0.75

230

0.92

480

460

0.92

600

575

0.92

Advertising