Johnson Controls SA PD 180 THRU 240 User Manual

Page 21

Advertising
background image

430645-YIM-D-0610

Johnson Controls Unitary Products

21

Defrost Operation

The defrost control board (DC) utilizes a time/temperature
defrost scheme. The DC repeats normal heating run cycles,
which must be completed, until one of the following conditions
is met and the DC enters defrost mode:

1.

The DC satisfies its accumulated minimum run time. This
is factory set at 60 minutes, but is field adjustable to 30, 60
or 90 minutes.

2.

The defrost switch(es) is closed. This normally open
switch is set to close at 28° F (+/-3°).

When the DC enters defrost mode, its on-board defrost relays
are powered. This energizes the reversing valve solenoid, de-
energizes the condenser fan motors and energizes the unit's
optional electric heater. The DC remains in defrost mode until
either of the following two conditions are met:

1.

Both of the liquid line thermostats are open. Each is set to
open at 55 degrees (+/- 3).

2.

The maximum defrost run time of 10 minutes is met.

The DC also contains a set of test pins. Placing a jumper
across these pins will result in the following actions:

• If the ASCD timer is active, it is now bypassed, allowing

the compressor to run.

• If the DC is in a lockout condition, the lockout is reset.

• If the compressor is running, the DC is forced into defrost

mode. The control will remain in defrost mode as long as
the jumper is in place. When the jumper is removed, the
control will terminate defrost mode.

NOTE: The DC has two flash codes that only initiate if the

jumper between the two pressure switch terminals is
removed or broken.

Blower Operation

After completing the specified time for fan on-delay, UCB closes
the coil of relay BR1.

• Relay BR1 sends a 24V signal to G1 of terminal block

TB2. It may be used to control operation of an indoor
blower.

The UCB disables the signal to BR1 after completing the fan
off-delay period.

Figure 9: Fan Orientation, Control Box End

Rear

Front

Rear

Front

2

1

2

1

4

3

Table 10: PC090 thru 240 Unit Control Board Flash Codes

FLASH CODE

DESCRIPTION

GREEN

LED

16

RED

LED

8

RED

LED

4

RED

LED

2

RED

LED

1

On Steady

This is a Control Failure

-

-

-

-

-

1 Flash

Not Applicable

-

-

-

-

-

2 Flashes

Control waiting ASCD

1

1. Non-alarm condition.

Flashing

Off

Off

On

Off

3 Flashes

HPS1 Compressor Lockout

Off

Off

Off

On

On

4 Flashes

Not Applicable

-

-

-

-

-

5 Flashes

LPS1 Compressor Lockout

Off

Off

On

Off

On

6 Flashes

Not Applicable

-

-

-

-

-

7 Flashes

FS1 Compressor Lockout

2

2. Freeze - stat not applicable.

Off

Off

On

On

On

8 Flashes

Not Applicable

-

-

-

-

-

10 Flashes

Compressors Locked Out on Low Outdoor Air Temperature

1

Flashing

On

Off

On

Off

12 Flashes

Unit Locked Out due to Fan Overload Switch Failure

Off

On

On

Off

Off

13 Flashes

Compressor Held Off due to Low Voltage

1

Flashing

On

On

Off

On

14 Flashes

EEPROM Storage Failure

Off

On

On

On

Off

OFF

No Power or Control Failure

Off

Off

Off

Off

Off