Figure 1: Corner Weights & Center Of Gravity

NOTE: Front of unit is considered the side having the control

box.

Concrete piers can also support ground level units. These piers
should (1) extend below the frost line, (2) be located under each
of the section's four corners, and (3) be sized to carry the load
of the corner it supports.

On either rooftop or ground level installations, rubber padding
can be applied under the unit to lessen any transmission of
vibration.

Holes are provided in the base rails for bolting the unit to its
foundation.

For ground level installations, precautions should be taken to
protect the unit from tampering and unauthorized persons from
injury. Screws on access panels will prevent casual tampering.
Further safety precautions such as a fenced enclosure or
locking devices on the panels may be advisable. Check local
authorities for safety regulations.

Table 3:

Corner Weights & Center of Gravity

Model

Weight (lbs.)

Center of Gravity (in.)

4 Point Load Location (lbs.)

Shipping

Operating

X

Y

A

B

C

D

PC090

421

430

17.3

33

110

130

103

87

PC120

543

574

16.4

32.3

153

161

134

127

PC180

947

968

32.5

33

266

274

217

211

PD180

921

942

34

32.5

243

275

225

199

PC240

1116

1152

32.1

30.8

300

301

276

275

PD240

1090

1126

31.2

31.8

311

295

253

267

DIM X

DIM Y

LENGTH

WIDTH

C

A

B

D

CG

FRONT

RIGHT

REAR

LEFT

CG

DIM X

DIM Y

LENGTH

WIDTH

C

B

A

D

FRONT

REAR

LEFT

RIGHT