Cooling charging curves – Johnson Controls SA PD 180 THRU 240 User Manual

Page 28

Advertising
background image

430645-YIM-D-0610

28

Johnson Controls Unitary Products

Figure 13: PC180 Charging Chart

Figure 14: PD180 Charging Chart

Cooling Charging Curves

PC180

200

300

400

500

600

120

130

140

150

160

170

180

Suction Pressure (psi)

Discharge Pressure (psi)

1. Make sure that all condenser fans are running when charging.
2. This chart is applicable to unit with the TXV’s left to the factory setting. If the TXV’s have been
adjusted in the field, the charging chart may no longer apply.

115°

95°

65°

75°

85°

105°

Outdoor Air Entering Condenser (F)

Cooling Charging Curves

PD180

200

300

400

500

600

120

130

140

150

160

170

180

Suction Pressure (psi)

Discharge Pressure (psi)

Outdoor Air Entering Condenser (F)

1. Make sure that all condenser fans are running when charging.
2. This chart is applicable to unit with the TXV’s left to the factory setting. If the TXV’s have been
adjusted in the field, the charging chart may no longer apply.

115°

105°

95°

75°

85°

65°