• Contactor M4 controls outdoor fans ODFAN3 & 4.

If the initial call for cooling requires both stages (Y1 and Y2), the
UCB will delay the second stage by 30 seconds to avoid an
excessive power inrush.

When the call for cooling (Y2) is satisfied, the UCB disables the
signal to RY2 and M2 as long as the specified minimum run
time (ASCD) has elapsed.

When the call for cooling (Y1) is satisfied, the UCB disables the
signal to RY1 and M1 as long as the specified minimum run
time (ASCD) has elapsed.

Low Ambient Cooling

These units are factory equipped with low ambient switches
that work through the Simplicity control board to operate the
compressors and condenser fans normally to 40ºF ambient
temperature. The Electronic Low Ambient Controller
2LA04703000 Accessory is designed to assure safe operation
through condenser head pressure regulation down to 0ºF
ambient temperature.

Low Ambient Control Operation

• A call for cooling closes contactor M3 which energizes all

condenser fans. The Low Ambient Control starts all fans
at full speed then adjusts according to the liquid line
temperature.

Refer to the appropriate 2LA low ambient kit instructions for
additional detail on the factory or field installed low ambient kit
and its operation.

Heating Sequence of Operation

General

Heat pump models are to be matched with air handlers of
equivalent tonnage ratings. Twinning of heat pumps and air
handlers is not recommended.

A two stage thermostat is required to operate the heat pump in
heating mode.

All reversing valves are de-energized during normal heating
mode. They are energized only during cooling and defrost
modes.

The heat pump operates all compressors during a first stage
call for heating unless locked out by the Unit Control Board
(UCB).

First Stage Heating Operation

When the thermostat calls for first stage heating (W1):

• The Simplicity control board (UCB) goes into a five minute

ASCD timer delay.

• When the ASCD time delay is satisfied, the UCB closes its

internal compressor relay contact, thus energizing the
contacts of relay RY1 and contactor M1.

• Relay RY1 has two functions: 1) control the operation of

crankcase heater CCH1, and 2) control the 24V output
signal to S1 on terminal block TB2.

• Contactor M1 controls compressor COMPR1.

• Relay RY3 (RY2 for PC090 model) toggles the 24V signal

from the "O" terminal of DC to the "Y" terminal assuring
the reversing valve cannot be energized except during
defrost.

• Concurrently, a 24V signal is sent to one of the "CFAN"

terminals of DC. The output signal from the remaining
"CFAN" terminal closes the coil of contactor M3.

• Contactor M3 controls outdoor fans ODFAN1 & 2 (all

models) and ODFAN3 & 4 (PC180-240).

(PC120-240; PD180-240 models)

• After a two second delay, the UCB energizes the contacts

of relay RY2 and contactor M2.

• Relay RY2 has two functions: 1) control the operation of

crankcase heater CCH2, and 2) control the 24V output
signal to S2 on terminal block TB2.

• Contactor M2 controls compressor COMPR2.

(PD180-240 models only)

• Concurrently, a 24V signal is sent to one of the "CFAN"

terminals of defrost control board DC2. The output signal
from the remaining "CFAN" terminal closes the coil of
contactor M4.

• Contactor M4 controls outdoor fans ODFAN3 & 4.

Second Stage Heating Operation

When the thermostat calls for second stage heating (W2):

• A 24V signal passes through UCB sending an input signal

to the "W" terminal of DC. This signal passes through DC
as an output signal to the "66" terminal of TB2 to be used
as a control signal for first stage electric heat.

Emergency Heating Operation

When the thermostat calls for emergency heating (EMER):

• The UCB de-energizes all compressor relays and

contactors.

• A 24V signal passes through UCB sending an input signal

to the "W" terminal of DC. This signal passes through DC
as an output signal to the "66" terminal of TB2 to be used
as a control signal for first stage electric heat.

• The normally closed contacts of M1-AUX and M2-AUX

(PC120-240; PD180-240 models only) send a 24V output
signal to the "60" terminal of TB2 to be used as a control
signal for second stage electric heat.