Electrical data – Johnson Controls SA PD 180 THRU 240 User Manual

Page 9

Advertising
background image

430645-YIM-D-0610

Johnson Controls Unitary Products

9

Electrical Data

Table 5:

Electrical Data - Outdoor Unit - HP Without Powered Convenience Outlet

Model

Compressors

Outdoor Fan Motor

Pwr Conv Outlet

Minimum

Circuit

Ampacity

1

Maximum
Fuse Size

(A)

2

Power

Supply

Qty

RLA

(each)

MCC

(each)

LRA

(each)

Power

Supply

HP

Qty

FLA

(each)

FLA

PC090

208/230-3-60

1

25.0

39

164

208/230-1-60

1/3

2

2.1

-

35.5

45

460-3-60

1

12.2

19

100

460-1-60

1/3

2

1.2

-

17.6

25

575-3-60

1

9.0

14

78

575-1-60

1/3

2

0.9

-

13.1

20

PC120

208/230-3-60

2

18.1

28.3

137

208/230-1-60

3/4

2

3.0

-

46.8

60

460-3-60

2

9.0

14.0

62

460-1-60

3/4

2

1.6

-

23.5

30

575-3-60

2

6.8

10.6

50

575-1-60

3/4

2

1.4

-

18.0

20

PC180

208/230-3-60

2

25.0

39

164

208/230-1-60

1/3

4

2.1

-

64.7

80

460-3-60

2

12.2

19

100

460-1-60

1/3

4

1.2

-

32.2

40

575-3-60

2

9.0

14

78

575-1-60

1/3

4

0.9

-

24.0

30

PD180

208/230-3-60

2

25.0

39

164

208/230-1-60

1/3

4

2.1

-

64.7

80

460-3-60

2

12.2

19

100

460-1-60

1/3

4

1.2

-

32.2

40

575-3-60

2

9.0

14

78

575-1-60

1/3

4

0.9

-

24.0

30

PC240

208/230-3-60

2

30.1

47

225

208/230-1-60

3/4

4

3.0

-

79.8

100

460-3-60

2

16.7

26

114

460-1-60

3/4

4

1.6

-

44.0

60

575-3-60

2

12.2

19

80

575-1-60

3/4

4

1.4

-

32.9

45

PD240

208/230-3-60

2

30.1

47

225

208/230-1-60

3/4

4

3.0

-

79.8

100

460-3-60

2

16.7

26

114

460-1-60

3/4

4

1.6

-

44.0

60

575-3-60

2

12.2

19

80

575-1-60

3/4

4

1.4

-

32.9

45

1.

Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.

2. Maximum fuse or maximum circuit breaker (HACR type per NEC).

Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.

Table 6:

Electrical Data - Outdoor Unit - HP With Powered Convenience Outlet

Model

Compressors

Outdoor Fan Motor

Pwr Conv Outlet

Minimum

Circuit

Ampacity

1

Maximum
Fuse Size

(A)

2

Power

Supply

Qty

RLA

(each)

MCC

(each)

LRA

(each)

Power

Supply

HP

Qty

FLA

(each)

FLA

PC090

208/230-3-60

1

25.0

39

164

208/230-1-60

1/3

2

2.1

10.0

45.5

60

460-3-60

1

12.2

19

100

460-1-60

1/3

2

1.2

5.0

22.6

30

575-3-60

1

9.0

14

78

575-1-60

1/3

2

0.9

4.0

17.1

25

PC120

208/230-3-60

2

18.1

28.3

137

208/230-1-60

3/4

2

3.0

10.0

56.8

70

460-3-60

2

9.0

14.0

62

460-1-60

3/4

2

1.6

5.0

28.5

35

575-3-60

2

6.8

10.6

50

575-1-60

3/4

2

1.4

4.0

22.0

25

PC180

208/230-3-60

2

25.0

39

164

208/230-1-60

1/3

4

2.1

10.0

74.7

90

460-3-60

2

12.2

19

100

460-1-60

1/3

4

1.2

5.0

37.2

45

575-3-60

2

9.0

14

78

575-1-60

1/3

4

0.9

4.0

28.0

35

PD180

208/230-3-60

2

25.0

39

164

208/230-1-60

1/3

4

2.1

10.0

74.7

90

460-3-60

2

12.2

19

100

460-1-60

1/3

4

1.2

5.0

37.2

45

575-3-60

2

9.0

14

78

575-1-60

1/3

4

0.9

4.0

28.0

35

PC240

208/230-3-60

2

30.1

47

225

208/230-1-60

3/4

4

3.0

10.0

89.8

110

460-3-60

2

16.7

26

114

460-1-60

3/4

4

1.6

5.0

49.0

60

575-3-60

2

12.2

19

80

575-1-60

3/4

4

1.4

4.0

36.9

45

PD240

208/230-3-60

2

30.1

47

225

208/230-1-60

3/4

4

3.0

10.0

89.8

110

460-3-60

2

16.7

26

114

460-1-60

3/4

4

1.6

5.0

49.0

60

575-3-60

2

12.2

19

80

575-1-60

3/4

4

1.4

4.0

36.9

45

1.

Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.

2. Maximum fuse or maximum circuit breaker (HACR type per NEC).

Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.