Masonry or prefabricated chimney conversion – Jotul GF300 DV User Manual

Page 13

Advertising
background image

13

Masonry or Prefabricated Chimney
Conversion

The GF 300 DV is approved for use with Simpson Dura-
vent Chimney Kit #934 in a masonry chimney or a
prefabricated solid fuel listed chimney.
These installation requirements must be followed:
1. Use the guidelines for Coaxial Vent Termination

appropriate for your gas type on pages 11 - 12.

2. In masonry chimney, a fireclay liner or listed steel

liner, must be present the entire length of the chim-
ney.

3. Chimney height should not exceed 35 ft. (10.67 m).
4. The liner must have an inside dimension of 6” round

or greater. (USE KIT #934)

5. Prefabricated chimneys must be UL 103 or ULC S-629

listed and have a minimum INSIDE diameter of 6
inches, (150 mm). Prefabricated chimneys must be
listed for the specific Simpson Dura-Vent Chimney
Conversion Kit. (USE KIT #931, #932, or #933)

Figure 16. Vent System through a masonry chimney
using the Simpson Dura-Vent Chimney Conversion Kit
#934. May also be used in listed prefabricated chimneys.
Drawing is for illustrative purposes only - DO NOT VENT
TWO APPLIANCES INTO A SINGLE CHIMNEY.

#991 Vertical

Termination Cap

Cap Adaptor-

included in

#934 Kit

Support/Wall

Thimble Cover -

included

in#934 Kit

Exhaust

Gas

Intake Air

Use Standard

Simpson

Dura-Vent GS

Pipe from

stove to

thimble

4” Flex Pipe

not included

in kit

IMPORTANT NOTICE

THE USE OF AN EXISTING CHIMNEY

AS AN AIR INTAKE IS NOT COVERED

UNDER THE ANSI Z21.88-1999-CSA

2.33-M99 TEST METHODS AND RE-

SULTING ITS/WHI PRODUCT CERTIFI-

CATION. THE CODE AUTHORITY

HAVING JURISDICTION MUST BE

CONSULTED PRIOR TO PROCEEDING

WITH THIS INSTALLATION METHOD.