2 procedure – Siemens SIMATIC NET CP 343-1 User Manual

Page 14

Advertising
background image

english

12

Product information CP 343–1

C79000–Z8964–C038–05

2.2

Procedure

Steps in Installation

Installing the CP 343-1 involves the following steps.

S

Plug in the CP 343-1 and secure it with the screws (make sure that the
bus connector between the CPU/IM and CP 343-1 is present).

S

Attach the CP 343-1 to Industrial Ethernet as illustrated in Section 2.3.

S

Connect a 24 V power supply.

Note

Make sure that you use the same voltage source as for the CPU or
IM 361.

Note

The two front panels must be kept closed during operation. The module
must be installed so that its upper and lower ventilation slits are not
covered, allowing adequate ventilation.

Configuration

To initialize the CP 343-1 for communication services, use the configuration
tool NCM S7 for Industrial Ethernet.

PG/PC Connection

You can connect the programming device when configuring the CP as
follows:

S

via MPI

S

via Industrial Ethernet
If you configure the module via Industrial Ethernet, the CP 343-1 must
already have a MAC address, in other words the hardware configura-
tion of the CP 343-1 must already have been downloaded via the MPI
interface (for details of node initialization, see /8/).