14_

installation and external connection

installation and external connection

Output Connection

- According to the operation mode, the Door Lock type is classifi ed in two: NC (Normal close) and NO

(Normal Open). Make the connection as appropriate.

- To prevent a risk of voltage surge during the lock operation, it is recommended to use the bypass diode.

- If the Door Lock type is POWER FAIL SAFE

Connect the COM (common) line of the Door Lock relay to DC +12V.

Connect the plus (+) line of the Door Lock to the Normal Close (NC) line of the Door Lock relay.

Connect the minus (-) line of the Door Lock to the grouding line, GND.

- If the Door Lock type is POWER FAIL SECURE

Connect the COM (common) line of the Door Lock relay to DC +12V (red).

Connect the plus (+) line of the Door Lock to the Normal Open (NO) line of the Door Lock relay.

Connect the minus (-) line of the Door Lock to the grounding line, GND.

Alarm Device Connection

Connect the COM line of the alarm device relay to DC +12V.

Connect the plus (+) line of the alarm device to NO.

Connect the minus (-) line of the alarm device to the grounding line, GND.

1.

2.

3.

1.

2.

3.

1.

2.

3.

+

-

+

-

1N4004 ~ 1N4007 or equiv.

Cathode

Anode

+12V

GND

+12V

GND

COM

NO

NC

COM

Normal
Open

Normal
Close