The intake air Tee fitting is factory installed with the 1/2 inch

branch and hose barb angled to the right at approximately 130°

when viewed from the end, see Figure 16. The Tee fitting's

1/2 inch branch and hose barb must not be angled any lower

(towards the ground) than this factory specification. Angling

higher, up to a 90° position, will not adversely affect operation

and is acceptable.
inspect/adjust intake air tee fitting
inspect the angle of the Tee fitting's 1/2 inch branch and hose

barb while viewing from the end of the Tee, see Figure 16. if the

angle of the Tee fitting 1/2 inch branch and hose barb is lower

than shown, adjustment will be necessary. To adjust the intake

air Tee fitting angle follow the steps listed below.
adjustment procedure:
1. Ensure the water heater is turned off at the on/off switch on

the front of the water heater.

2. Disconnect the blocked intake Air switch sensing tube, see

Figure 4 on page 9 for location.

3. Loosen the large hose clamp on the Fernco coupling that

connects the intake air connection pipe to the Combustion

blower, see Figure 17.

4. Adjust the angle of the Tee fitting so that the 1/2 inch branch

and hose barb are at the proper angle as shown in Figure 16.

5. retighten the large hose clamp on the Combustion blower

intake air Fernco coupling,

6. reconnect the blocked intake Air switch sensing tube making

sure the sensing tube is securely connected at both ends and

is not kinked.

INTAKE AIR CONNECTION PIPE

199,000 & 250,000 Btu/hr MODELS

LARGE HOSE

CLAMP

3 INCH PVC

INTAKE AIR

TEE FITTING

FERNCO

COUPLING

figure 17

suf 199 & suf 250 intake air connection

SUF 100 199 and SUF 100 250 models are factory equipped

with a unique Combustion blower and intake air connection Tee

fitting. The Tee is a 3" x 3" x 1/2" fitting. The intake air connection

Tee fitting has a hose barb installed in the 1/2 inch branch to

connect the blocked intake Air switch sensing tube, see Figure

15.

FACTORY INSTALLED

INTAKE AIR TEE FITTING

COMBUSTION BLOWER ASSEMBLY

199,000 & 250,000 Btu/hr MODELS

COMBUSTION BLOWER

1/2 INCH

BRANCH

HOSE BARB FITTING FOR

BLOCKED INTAKE AIR

SWITCH SENSING TUBE

FERNCO

COUPLING

figure 15

Ensure the hose barb installed in the Tee fitting

is not facing

down towards the ground (180° - 6 o'clock position) before venting

installation begins. The barb fitting must be angled between 90°

and no more than 130° as shown in Figure 16. if the barb fitting

is facing down, residual condensate that occasionally forms in

the intake air pipe can drain into the blocked intake Air switch

through the attached sensing tube and damage the switch. This

condition can also lead to blocked intake Air fault conditions and

associated control system lock outs.

90° TO 130°

CORRECT ORIENTATION

INTAKE AIR TEE FITTING

END VIEW

figure 16