Supply gas pressure adjustment, Manifold gas pressure adjustment, Supply – State Industries ULTRA FORCE 101 User Manual

Page 54: Supply gas pressure adjustment on

Advertising
background image

54

supply gas pressure adjustment

Fire and Explosion Hazard

Turn off gas lines during installation.
Contact a qualified installer or service

agency for installation and service.

Excessive gas pressure to gas valve can

cause serious injury or death.

Do not use water heater with any gas

other than the gas shown on the rating

label.

Supply gas pressure shall be measured while the water heater is

not firing (static pressure) aND while the water heater is firing at

full capacity (dynamic pressure).
if the supply gas pressure to the water heater is not between the

required minimum and maximum values given in Table 3 on page

12 adjust the supply gas regulator as necessary. Adjust the supply

gas regulator(s) per the regulator manufacturer’s instructions to

achieve the required “static” and “dynamic” supply gas pressure.
multiple water heater installations:

in multiple water heater installations or in installations where

the installed water heater(s) share a common gas supply main

with other gas fired appliances; the supply gas pressures shall

be measured at each water heater with all gas fired appliances

connected to a common main firing at full capacity.
On multiple water heater installations the supply gas line

regulators shall be adjusted to provide gas pressure to each

water heater within the minimum and maximum supply pressure

requirements listed in Table 3 on page 12 with all gas fired

appliances connected to a common gas main firing at full capacity.
note: A pressure drop of more than 1.5” W. C. (0.37 kPa) when

the main burner ignites is an indication of an inadequate supply

of gas and can lead to ignition failure, rough starts and/or rough

operation. if a drop of more than 1.5” W. C. (0.37 kPa) in supply

gas pressure occurs when the main burner ignites, ensure the

supply gas lines and regulator(s) are properly sized and installed.

See the requirements for Supply Gas regulator and Gas Supply

Systems on page 14. See Supply Gas Line installation on

page 39 and Supply Gas regulator on page 14. Ensure all

requirements and installation instructions are maintained.
manifold gas pressure adjustment

Fire and Explosion Hazard

Gas and carbon monoxide detectors are

available.

Overfiring could result in fire or

explosion.

Under no circumstances should the

input exceed the rate shown on the

water heater’s rating label.

Breathing Hazard - Carbon Monoxide Gas

Breathing carbon monoxide can cause brain damage or

death. Always read and understand instruction manual.

Under no circumstances should

the input exceed the rate shown

on the water heater’s rating label.

Overfiring could result in damage to

the water heater and sooting.

Gas and carbon monoxide detectors

are available.

Ensure the "dynamic" supply gas pressure is above the

minimum requirements in Table 3 on page 12 before any

adjustments are made to the manifold gas pressure. Attempts

to adjust manifold gas pressure during periods of low supply gas

pressure could result in overfiring when the supply gas pressure

returns to normal. See Supply Gas Pressure Adjustment on this

page.
note: manifold gas pressure is non-adjustable on SUF 100

199 and SUF 100 250 models. The manifold gas pressure on

these models is factory set and cannot be field adjusted. if the

manifold gas pressure readings taken on these models is off by

more than ± 0.3" W. C. from the listed values in Table 3 on page

12 call the technical support phone number listed on the back

cover of this manual for further assistance.
Follow the steps below to adjust the manifold gas pressure

on SUF 100 120 and SUF 100 150 models:

1. Follow the instructions for initial Start Up on page 52

to connect manometers to the supply and manifold gas

pressure taps and to start the water heater.

2. remove the manifold gas pressure regulator cover

screw, see Figure 57 on page 53.

3. Using a small flat tip screw driver turn the adjustment

screw clockwise to increase manifold gas pressure and

counter clockwise to decrease manifold gas pressure.

note: Turn the manifold gas pressure adjustment

screw in small increments (no more than 1/4 turn) and

allow the manifold gas pressure to stabilize for several

minutes before making further adjustments.

4. replace the gas pressure regulator cover screw.

5. Cycle the burner on and off several times to check

operation.

Advertising
This manual is related to the following products: