Installation requirements, Gas supply systems, Supply gas regulator – State Industries ULTRA FORCE 101 User Manual

Page 14: Power supply, Gas supply systems on

Advertising
background image

14

1. Positive lock-up gas pressure regulators must be rated at or

above the input btu/hr rating of the water heater they supply.

2. Supply gas regulators shall have inlet and outlet connections

not less than the minimum supply gas line size for the water

heater they supply. See Table 8, page 23.

3. Positive lock-up gas pressure regulator(s) should be installed

no closer than 3 feet (1 meter) and no farther than 8 feet (2.4

meters) from the water heater’s inlet gas connection.

4. After installing the positive lock-up gas pressure regulator(s)

an initial nominal supply pressure setting of 7.0” W.C. while the

water heater is operating is recommended and will generally

provide good water heater operation. Some addition adjustment

maybe required later to maintain a steady gas supply pressure.

5. When installing multiple water heaters in the same gas

supply system it is recommended that individual positive

lock-up gas pressure regulators be installed at each unit

from the supply gas connection on the water heater.

power supply

The water heaters covered in this manual require a 120 VAC,

1Ø (single phase), 60Hz, 15 amp power supply and must also

be electrically grounded in accordance with local codes or, in the

absence of local codes, with the National Electrical Code, ANSi/

NFPA 70 or the Canadian Electrical Code, CSA C22.1.

power fluctuations and electrical noise

The water heater’s control system requires a source of stable

clean electricity for proper operation. Connecting the water heater

to a branch circuit that is subject to fluctuations in voltage level or

electrical line noise such as Emi (electro magnetic interference)

or rFi (radio frequency interference) may cause erratic control

system operation and malfunction.
A high quality power supply filter/suppressor such as the kleen Line

model SELF/T-10 Series SC-L or equivalent must be installed if the

above conditions exist. Call the technical support phone number

listed on the back cover of this manual for more information.
note: malfunctions caused by the power supply and the costs to

install power supply filters are not covered under the limited warranty.

dedicated power wiring and breakers

Dedicated power supply wires, ground wiring and dedicated

circuit breakers often prevent electrical line noise and should be

considered when installing the water heater.

polarity sensitiVe

The control system on the water heaters covered in this manual

is polarity sensitive; electronic flame sensing requires correct

polarity. The control system is programmed to monitor the

incoming power supply. if the Hot and Neutral wires in the 120

VAC power supply are reversed, the control system will declare

a Fault condition and lock out, heating operation will be disabled

until the power supply is correctly wired. The control system will

display the “AC reversed” Fault message on the LCD.
See Electrical Wiring on page 41 for installation instructions.

gas supply systems

Low pressure building gas supply systems are defined as those

systems that cannot under any circumstances exceed 14”

W.C. (1/2 PSi Gauge). These systems do not require pressure

regulation. measurements should be taken to insure that gas

pressures are stable and fall within the requirements stated on the

water heater rating plate. readings should be taken with all gas

burning equipment off (static pressure) and with all gas burning

equipment running at maximum rate (dynamic pressure). The

gas supply pressure must be stable within 1.5” W.C. from static

to dynamic pressure to provide good performance. Pressure

drops that exceed 1.5” W.C. may cause rough starting, noisy

combustion or nuisance outages. increases or spikes in static

pressure during off cycles may cause failure to ignite or in severe

cases damage to appliance gas valves. if your low pressure

system does NOT meet these requirements, the installer is

responsible for the corrections.
High Pressure building supply systems use pressures that

exceed 14” W.C. (1/2 PSi Gauge). These systems must use field

supplied regulators to lower the gas pressure to less than 14”

W.C. (1/2 PSi Gauge). Water heaters require gas regulators that

are properly sized for the water heater input and deliver the rating

plate specified pressures. Gas supply systems where pressure

exceeds 5 PSi often require multiple regulators to achieve desired

pressures. Systems in excess of 5 PSi building pressure should

be designed by gas delivery professionals for best performance.

Water heaters connected to gas supply systems that exceed 14”

W.C. (1/2 PSi Gauge) at any time must be equipped with a gas

supply regulator.
All models require a minimum gas supply pressure of 4.9" W.C.

for natural gas and 11.0" W.C. for propane gas. The minimum

supply pressure is measured while gas is flowing (dynamic

pressure). The supply pressure should never fall below 4.9"

W.C. for natural gas and 10.5" W.C. for propane gas. The supply

pressure should be measured with all gas fired appliances

connected to the common main firing at full capacity. if the supply

pressure drops more than 1.5” W.C. as gas begins to flow to

the water heater then the supply gas system including the gas

line and/or the gas regulator may be restricted or undersized.

See Supply Gas regulator section and Gas Piping section of

this manual. The gas valve on all models has a maximum gas

supply pressure limit of 14” W.C. The maximum supply pressure

is measured while gas is not flowing (static pressure).
14” W.C. The maximum supply pressure is measured while gas

is not flowing (static pressure).

supply gas regulator

The maximum allowable gas supply pressure for this water

heater is 10.5 inches W.C. (2.62 kPa) for natural gas and 14.0

inches W.C. (3.49 kPa) for propane. install a positive lock-up gas

pressure regulator in the gas supply line if inlet gas pressure can

exceed these pressures at any time.
if a positive lock-up regulator is required follow these instructions:

installation reQuirements

Advertising
This manual is related to the following products: