Commonwealth of massachusetts, Commonwealth – State Industries ULTRA FORCE 101 User Manual

Page 21

Advertising
background image

21

commonwealth of massachusetts

For all side wall terminated, horizontally vented power vent, direct

vent, and power direct vent gas fueled water heaters installed in

every dwelling, building or structure used in whole or in part for

residential purposes, including those owned or operated by the

Commonwealth and where the side wall exhaust vent termination

is less than seven (7) feet above finished grade in the area of

the venting, including but not limited to decks and porches, the

following requirements shall be satisfied:

installation of carbon monoxide detectors

At the time of installation of the side wall horizontal vented

gas fueled equipment, the installing plumber or gasfitter shall

observe that a hard wired carbon monoxide detector with an

alarm and battery back-up is installed on the floor level where

the gas equipment is to be installed. in addition, the installing

plumber or gasfitter shall observe that a battery operated or

hard wired carbon monoxide detector with an alarm is installed

on each additional level of the dwelling, building or structure

served by the sidewall horizontal vented gas fueled equipment.

it shall be the responsibility of the property owner to secure the

services of qualified licensed professionals for the installation of

hard wired carbon monoxide detectors.

in the event that the side wall horizontally vented gas fueled

equipment is installed in a crawl space or an attic, the hard wired

carbon monoxide detector with alarm and battery back-up may

be installed on the next adjacent floor level.

in the event that the requirements of this subdivision can not

be met at the time of completion of installation, the owner shall

have a period of thirty (30) days to comply with the above

requirements provided that during said thirty (30) day period, a

battery operated carbon monoxide detector with an alarm shall

be installed.

approVed carbon monoxide detectors

Each carbon monoxide detector as required in accordance with

the above provisions shall comply with NFPA 720 and be ANSi/

UL 2034 listed and CSA certified.

signage

A metal or plastic identification plate shall be permanently

mounted to the exterior of the building at a minimum height of

eight (8) feet above grade directly in line with the exhaust vent

terminal for the horizontally vented gas fueled heating appliance

or equipment. The sign shall read, in print size no less than one-

half (1/2) inch in size,

“gas Vent directly below. keep

clear of all obstructions.”

installation reQuirements - commonwealth of massachusetts

inspection

The state or local gas inspector of the side wall horizontally

vented gas fueled equipment shall not approve the installation

unless, upon inspection, the inspector observes carbon

monoxide detectors and signage installed in accordance with the

provisions of 248 Cmr 5.08(2)(a) 1 through 4.

exemptions

The following equipment is exempt from 248 Cmr 5.08(2)(a)1

through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not

required To be Vented” in the most current edition of NFPA

54 as adopted by the board; and

2. Product Approved side wall horizontally vented gas fueled

equipment installed in a room or structure separate from the

dwelling, building, or structure used in whole or in part for

residential purposes.

manufacturer reQuirements - gas

eQuipment Venting system proVided

When the manufacturer of Product Approved side wall

horizontally vented gas equipment provides a venting system

design or venting system components with the equipment, the

instructions provided by the manufacturer for installation of the

equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system

design or the venting system components; and

2. A complete parts list for the venting system design or venting

system.

manufacturer reQuirements - gas

eQuipment Venting system not proVided

When the manufacturer of a Product Approved side wall

horizontally vented gas fueled equipment does not provide the

parts for venting the flue gases, but identifies “special venting

systems,” the following requirements shall be satisfied by the

manufacturer:
1. The referenced “special venting system” instructions shall

be included with the appliance or equipment installation

instructions; and

2. The “special venting systems” shall be Product Approved by

the board, and the instructions for that system shall include a

parts list and detailed installation instructions.

A copy of all installation instructions for all Product Approved

side wall horizontally vented gas fueled equipment, all venting

instructions, all parts lists for venting instructions, and/or all

venting design instructions shall remain with the appliance or

equipment at the completion of the installation.