Five metres of piping is supplied with the air conditioner(Optional).
This length can if necessary be:

Extended to a maximum of ten metres
Shortened as required

If more than five metres of piping is required:

The assembly cable must also be extended

Refrigerant must be added to the circuit by an
approved installer; otherwise, the indoor unit may
freeze

1

Make sure that you have the required tools available
(pipe cutter, reamer, flaring tool and pipe holder).

2

If you wish to shorten the piping, cut it using a pipe cutter, taking care to
ensure that the cut edge remains at a 90° angle with the side of the pipe,
and referring to the illustrations below for examples of edges cut correctly
and incorrectly.

3

To prevent any gas from leaking out, remove all burrs at the cut end of the
pipe, using a reamer.

4

Slide a flare nut on to the pipe and modify the flare.

Pipe

Outer Diameter (D)

Depth (A)

Liquid refrigerant

6.35 mm (1/4")

1.3 mm (5/100")

Gas refrigerant

9.52 mm (3/8")

1.8 mm (7/100")

Gas refrigerant

12.70 mm (1/2")

2.0 mm (8/100")

5

Check that the flaring is correct, referring to the illustrations below for
examples of incorrect flaring.

Inclined

Damaged Surface

Cracked

Uneven Thickness

6

Align the pipes to be connected and tighten the flare nuts first manually
and then with a wrench, applying the following torque.

Pipe

Outer Diameter

Torque (kg•cm)

Liquid refrigerant

6.35 mm (1/4")

160 (11 ft•lb)

Gas refrigerant 9.52 mm (3/8")

300 (21 ft•lb)

Gas refrigerant 12.70 mm (1/2")

500 (36 ft•lb)

7

For further details on how to connect up to the outdoor unit and purge the
circuit, refer to page 41.