Bus systems, 6 bus systems – Siemens FC700A User Manual

Page 14

Advertising
background image

Bus systems

14

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004


6 Bus

systems

In the FC700A fire detection system there are 5 communication levels:

I-Bus

Internal data bus between individual modules in the control unit (line modules,
control modules etc.)

C-Bus

Local data bus between control unit(s), control terminal(s) and Gateway(s)

SynoLOOP and SynoLINE600

Local detector bus; connects the detectors to the control unit

LON-Bus

Local data bus for floor repeater panels, mimic display converter and LON I/O
card

Data Bus

Local data bus for parallel indicator panel, synoptic panel or relay

K3I050

Gateway

FG700A

E3M111

SynoLOOP

E3M080

SynoLINE600

I-Bus

Control unit FC700A

Line modules

Control terminal

FT700A

E3H020

Building

management

system

ISO1745 Protocol

C-Bus

B3Q580/

B3Q590/

B3Q595

E3I040

LON-Bus

Databus

B3R051

or

K3R072/

K3G060

RS232

K3I110

In-/Outputs

E3I040

I-Bus

LON-Bus

CPU

B3Q700

Databus

Advertising