Auxiliary power supply, Configuration, Block diagram – Siemens FC700A User Manual

Page 26: Modules, 11 auxiliary power supply, 1 configuration, 2 block diagram, 3 modules, Fc700a

Advertising
background image

Auxiliary power supply

26

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004


11

Auxiliary power supply

11.1 Configuration

31

51

23

27

37

47

57

46

56

A

28

38

48

58

AX1210

AX1201

or

Mains

terminals

AX1210

AX1201

or

View A

E3C01

1

B2

F

020

Z3

I47

0

H38G310

Module chassis
view 'Modules'

Cabinet front view

absolutely essential

B2F020

Converter 115/230VAC

-> 29.6VDC/6A

E3C011

Battery charging module

AX1201 / AX1210
Batteries

Z3I470

Cable set, terminal strip

with card holder

11.2 Block

diagram

* TF = Temperature sensor for battery temperature monitoring

Mains

Basic emergency
power supply

Extension

B2F020

TF*

TF*

Batteries

AX12..

Batteries

AX12..

Monitoring via HW monitoring path

FC700A

Mains

B2F020

E3C011

E3C011

Battery charging unit

H38G310

Cascading

Details see document 007831, chapter 'Cascading principle'

To activate the supervision path of the E3C011, the device "Fu supply ext. supply
supervision" must be created in the tool SWE700A.

11.3 Modules

Component Order-No. Description

Notes

H38G310

484930

Housing set

Door without cut-out

B2F020

470588

Converter 115/230VAC -> 29,6VDC 6A

E3C011 505479 Battery

charging

unit

Z3I470

484341

Cable set with card holder

AX1201

225487

Battery 12V / 27Ah

Capacity based battery make 'ALARMCOM' (FIAMM)

AX1210

475570

Battery 12V / 15Ah

Advertising