Specify hardware required

23

Siemens Building Technologies

007836_a_en_--.doc

Fire & Security Products

03.2004


9

Specify hardware required

In order to be able to specify the hardware required, system key data must be
specified according the following procedure:

1. Specify number and type of detection lines

Dependent on:

Detector series

Number of detectors, input and output modules

Building structure


2. Specify number and type of fire control installations

Dependent on:

The fire protection installations to be activated

Location of the contacts (centralized or decentralized)

Individual types of contact (250VAC/10A or 30VDC/1A)


3. Specify number of operating units

Dependent on:

Operating concept

Parallel indicator panels, fire department control panels


4. Specify Accessories required

Dependent on:

Printer interface and printer

Remote transmission equipment

Gateway, etc.


5. Specify emergency power supply battery capacity

Dependent on:

Total quiescent current

Required emergency current operating period (according to country)

Type of remote transmission


6. Provide configuration sheet/sheets (see chapter 29)

Dependent on:

Select sheets corresponding to the configuration

Complete everything