Displaying tower information, Creating a descriptive infeed name, Displaying infeed information – Sentry Industries PT22 User Manual

Page 38: Displaying the sentry firmware version, Performing a warm boot

Advertising
background image

Displaying tower information

The Show Towers command displays information about the Sentry. This information includes the
absolute and descriptive Sentry names.

To display tower information:

At the Sentry: prompt, type show towers and press Enter.

Example

Sentry: show towers<Enter>
Tower Tower
ID Name
.A Florida_HQ_1

Creating a descriptive infeed name

The Set Infeed Name command assigns a descriptive name to an infeed. This descriptive name is
displayed when the Show Traps command is issued. See Displaying trap configuration information on
page 38 for more information on the Show Traps command.

To create a infeed name:

At the Sentry: prompt, type set infeed name, followed by the absolute infeed name, then the descriptive
name of up to 24 alphanumeric and other typeable characters (ASCII 33 to 126 decimal - spaces are not
allowed). Press Enter.

Example

The following command adds the descriptive name HQ_1_Infeed_A to the infeed on the Sentry:

Sentry: set infeed name .aa HQ_1_Infeed_A<Enter>

Displaying Infeed information

The Show Infeeds command displays information about all infeeds. This information includes the
absolute and descriptive infeed names.

To display tower information:

At the Sentry: prompt, type show infeeds and press Enter.

Example

Sentry: show infeeds<Enter>
Input Input
Feed ID Feed Name
.AA HQ_1_Infeed_A
.AB HQ_1_Infeed_B
.AC HQ_1_Infeed_C
.AD HQ_1_Infeed_D

Displaying the Sentry firmware version

The Version command displays the Sentry firmware version.

To display the firmware version:

At the Sentry: prompt, type version and press Enter.

Performing a warm boot

The Restart command performs a warm boot of the Sentry.

NOTE: System user/outlet/group/port configuration or outlet states are NOT changed or reset with this command.

To perform a warm boot:

At the Sentry: prompt, type restart and press Enter.

38

• Operations

Sentry PT22

Installation and Operations Manual

Advertising