Warning – Superior SDV35 User Manual

Page 17

Advertising
background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

17

Figure 29

- Top Vent - STRAIGHT

A Vent Restrictor, as shown in Figure 17 on

Page 13, must be used in this application

u

Ceiling Firestop /

Spacer (SV4.5VF)

40 feet

(12.2 meters)

Maximum

u

When using Secure Flex, use Firestop / Spacer

SF4.5VF

VERTICAL VENT FIGURES/TABLES

Notes:

• Secure Vent™ (rigid vent pipe) is shown

in the Figures; Secure Flex™ (flexible vent

pipe) may also be used.

• It is very important that the horizontal/in-

clined run be maintained in a straight (no

dips) and recommended to be in a slightly

elevated plane, in a direction away from

the fireplace of 1/4" rise per foot (20 mm

per meter) which is ideal, though rise per

foot run ratios that are smaller are acceptable

all the way down to at or near level.

SV4.5VF (Secure Vent), SF4.5VF (Secure

Flex) firestop/spacer must be used anytime

vent pipe passes through a combustible

floor or ceiling. SV4.5HF (Secure Vent),

SF4.5HF (Secure Flex) firestop/spacer must

be used anytime vent pipe passes through

a combustible wall.

Two 45 degree elbows may be used in place

of one 90 degree elbow. The same rise to

run ratios, as shown in the venting Figures

for 90 elbows, must be followed if 45 degree

elbows are used.

• AN ELBOW IS ACCEPTABLE AS 1 FOOT OF

VERTICAL RISE EXCEPT WHERE AN ELBOW

IS THE ONLY VERTICAL COMPONENT IN

THE SYSTEM (See Figure 38).

WARNING

Under No Circumstances, May Sepa-

rate Sections of Concentric Flexible

Vent Pipe Be Joined Together.

V

H

H

V

V1

Table B

H Maximum

V Minimum

feet

(meter)

feet

(meter)

5

(1.524)

Elbow Only

5

(1.524)

1

(0.305)

10

(3.048)

2

(0.610)

15

(4.572)

3

(0.914)

20

(6.096)

4

(1.219)

V + V

1

+ H = 40 feet (12.2 m) Max.

H = 20 feet (6.096 meters) Max.

u

Ceiling Firestop /

Spacer (SV4.5VF)

v

Wall Firestop/

Spacer (SV4.5HF)

u

When using Secure Flex, use Firestop /

Spacer SF4.5VF.

v

When using Secure Flex, use Firestop /

Spacer SF4.5HF.

Table A

H Maximum

V Minimum

feet

(meter)

feet

(meter)

2

(0.610)

1

(0.305)

4

(1.219)

2

(0.610)

6

(1.829)

3

(0.914)

8

(2.438)

4

(1.219)

V + H = 40 feet (12.2 meters) Max.

H = 8 feet (2.4 meters) Max.

Ratio V to H ratio is 1:2

Example: If 8 feet of (H) horizontal vent run

is needed, then 4 feet minimum (V) vertical

vent will be required.
This table shows a 1(V) to 2(H) ratio. For

every 1 foot of (V) vertical, you are allowed 2

feet of (H) horizontal run, up to a maximum

horizontal run of 8 feet.

Figure 30

- Rear Vent - ONE 90 DEGREE ELBOW

Figure 31

- Top Vent - TWO 90 DEGREE ELBOWS

Example: If 20 feet of (H) horizontal vent run

is needed, then 4 feet minimum of (V) vertical

vent will be required.

This table shows a 1(V) to 5(H) ratio. For

every 1 foot of (V) vertical, you are allowed 5

feet of (H) horizontal run, up to a maximum

horizontal run of 20 feet.

An elbow is acceptable as 1 foot of vertical

rise except where an elbow is the only vertical

component in the system. See Figure 38.

u

When using Secure Flex, use Firestop /

Spacer SF4.5VF.

u

Ceiling Firestop /

Spacer (SV4.5VF)

Advertising