Warning – Superior SDV35 User Manual

Page 21

Advertising
background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

21

H

H = 28 in. (711 mm) Maximum.

7 in. (178 mm)

When using Secure Flex,

use Firestop/Spacer

SF4.5HF

Wall Firestop/Spacer

(SV4.5HF)

H

V

Wall Firestop/Spacer

(SV4.5HF)

When using Secure Flex,

use Firestop/Spacer

SF4.5VF.

Ceiling

Firestop/Spacer

(SV4.5VF)

When using Secure Flex,

use Firestop/Spacer

SF4.5HF.

Figure 38

- Top Vent -

ONE 90 DEGREE ELBOW - ELBOW CONNECTION AT APPLIANCE

Figure 39

-

Top Vent - ONE 90 DEGREE ELBOW -

ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE

Figure 37

- Rear Vent - NO ELBOWS - Square Horizontal

Termination (SV4.5HT-2)

See Table 8 as an aid in venting component selection for a

particular range of exterior wall thicknesses.

See Table 8 as

an aid in venting

component selec-

tion for a particular

range of exterior

wall thicknesses.

H

Wall

Firestop/Spacer

(SV4.5HF)

V

When using Secure Flex,

use Firestop/Spacer

SF4.5HF

HORIZONTAL VENT FIGURES/TABLES

Notes:

• Secure Vent™ components (rigid vent pipe and terminal) are shown

in the Figures; Secure Flex™ components (flexible vent pipe and

terminal) may also be used.

Two 45 degree elbows may be used in place of one 90 degree elbow.

The same rise to run ratios, as shown in the venting Figures for 90

elbows, must be followed if 45 degree elbows are used.

SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must be

used anytime vent pipe passes through a combustible floor or ceiling.

SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer must

be used anytime vent pipe passes through a combustible wall.

• It is very important that the horizontal/inclined run be maintained

in a straight (no dips) and recommended to be in a slightly elevated

plane, in a direction away from the fireplace of 1/4" rise per foot (20

mm per meter) which is ideal, though rise per foot run ratios that are

smaller are acceptable all the way down to at or near level.

The tables show a 1(V) to 5(H) ratio up to a maximum horizontal run

of 20 feet except for installations where an elbow is the only vertical

vent section in the system (see Figure 38).

• AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT

WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE

SYSTEM. See Figure 38.

Square termination

(SV4.5HT-2)

shown

See Table 8 as an aid in venting component selection for a particular

range of exterior wall thicknesses.

WARNING

Under no circumstances, may separate sections of

concentric flexible vent pipe be joined together.

Table G

H Maximum

V Minimum

feet (meter) feet (meter)

5

(1.524)

1

(0.305)

10

(3.048)

2

(0.610)

15

(4.572)

3

(0.914)

20

(6.096)

4

(1.219)

V + H = 40 feet (12.2 m) Max.

H = 20 ft. (6.096 m) Max.

Square termination

(SV4.5HT-2) shown.

Square termination

(SV4.5HT-2) shown.

Table F

H Maximum

V Minimum

feet

(meter)

feet

(meter)

3

(0.914)

Elbow Only

Example: If 20 feet of (H) horizon-

tal vent run is needed, then 4 feet

minimum of (V) vertical vent will

be required.

This table shows a 1(V) to 5(H) ratio.

For every 1 foot of vertical, you are

allowed 5 feet of (H) horizontal run

up to a maximum (H) horizontal run

of 20 feet.

Venting Components Required for Various Exterior Wall Thick-

nesses, when using Square Termination Kit (SV4.5HT-2)

Vent Components Required Exterior Wall Thickness - inches (mm)
Termination Kit Only

6 to 9-1/4 (152 to 235)

Termination Kit and 6 In. Vent

Section (SV4.5L6)

10-3/4 to 14 (273 to 356)

Termination Kit and 12 in.

Vent Section (SV4.5L12)

16-3/4 to 20 (426 to 508)

Termination Kit and Tele-

scopic Section (SV4.5L12)

11-3/4 to 20 (299 to 508)

Table 8

Note: See Figure 36 showing wall thickness range

when using SV4.5HT-2 termination kit only.