Schneider Electric SURTD 3000 User Manual

Page 10

Advertising
background image

10

N

OTE

:

S

ETTINGS ARE MADE THROUGH SUPPLIED

P

OWER

C

HUTE SOFTWARE

,

OPTIONAL

S

MART

S

LOT

ACCESSORY CARDS

,

OR

T

ERMINAL

M

ODE

.

F

UNCTION

F

ACTORY

D

EFAULT

U

SER

S

ELECTABLE

C

HOICES

D

ESCRIPTION

Low Bypass Point

160 VAC

Output Voltage Setting

200 VAC:
160 - 185 VAC

208 VAC:
160 - 190 VAC

220 VAC:
160 - 195 VAC

230 VAC:
160 - 200 VAC

240 VAC:
160 - 205 VAC

Minimum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.

Output Voltage

XLJ models:
200 VAC

XLT models:
208 VAC

XLTW models:
220 VAC

XLI models:
230 VAC

200, 208, 220,
230, 240 VAC

Allows the user to select the on
on-line output voltage.

50 ± 3 Hz
50 ± 1 Hz
50 ± 0.1 Hz

60 ± 3 Hz
60 ± 1 Hz
60 ± 0.1 Hz

Output Frequency

Automatic

50 ± 3 Hz or
60 ± 3 Hz

50 ± 3 Hz or 60 ± 3 Hz

Sets the allowable UPS output
frequency. Whenever possible,
the output frequency tracks the
input frequency.

Number of External
Battery Packs

0

0 to 100

Defines the number of external
connected battery packs for
proper run time prediction.

Bypass Acceptable

Not required

Required/ Not required

Phase and frequency lock
required/not required before the
UPS will switch to bypass.