Editing Parameters

Siemens Building Technologies, Inc.

15

6. Press to access the index value. Use

and

to scroll through the index values and to

highlight the desired index value.

7. Press to confirm the new index value. The AOP returns to the parameter selection screen

so you can select another parameter, if desired.

8. To edit another indexed parameter, repeat Steps 3 to 6.

NOTES:

1.

Simultaneously press

and

, at any time, to return to the main menu.

2.

Simultaneously press

and

, at any time, to display the parameter help screens.

AOP Stored Parameter Sets

The AOP contains a battery-backed storage facility for storing up to 10 parameter sets that are
identified numerically from 00 to 09.

Only a parameter set containing parameter data can be edited. If the selected parameter set does
not contain parameter data, the AOP asks if the default parameter set should be copied to the
selected parameter set. When you confirm this request, the AOP copies only the editable
parameters to the selected parameter set; read-only parameters are accessed from the original
parameter location.

Editing AOP-Stored Parameter Sets

Use the following procedure to edit a parameter set:

1. From the main menu, use

and

to scroll through the list of options and to highlight the

Mode item. Press

to confirm the selection.

The AOP displays a mode menu so you can select the operating mode.

2. Use and

to scroll through the list of mode options and to highlight the Internal item.

Press

to confirm the selection.

The AOP displays an internal mode menu so you can select the internal mode function.

3. Press again to confirm the selection and to return to the main menu.

4. Use and

to scroll through the main menu and to highlight the Parameters item. Press

to confirm the selection.

The AOP displays an internal edit parameter set menu so you can select the desired
parameter set.

5. Use and

to scroll through the list of parameter sets and to highlight the desired

parameter set number.
You can now edit parameters associated with the selected parameter set.

Editing Internal AOP Parameter Set

1. Set

P0003=3 (expert parameter access level).