Siemens SED2 User Manual

Page 26

Advertising
background image

SED2 AOP Operating Instructions

18

Siemens Building Technologies

1. From the main menu, use

and

to scroll through the list of options and to highlight the

Download item.
Press

to confirm the selection. Press

to cancel the download process.

The AOP displays a download menu.

NOTE:

In master mode, the AOP prompts for selection of a specific SED2 VFD from a
list of the networked SED2 VFDs.

2. Use and

to scroll through the list of parameter sets and to highlight the parameter set

from which information will be copied.
Press

to confirm the selection.

3. The AOP displays a confirmation screen.

Press

to confirm the selection. Press

to cancel the download process.

4. The AOP displays a wait screen while the download process occurs.

5. On completion of the download process, the AOP returns to the main menu.

NOTES:

If the download fails, perform the following:

1. Reset VFD parameters: Commissioning Parameter P0010=30 for factory settings and

Factory Reset Parameter P0970=1 to reset all parameters to their default values.

2. Cycle VFD power off/on.

3. Repeat the download process.