User settings, 1 setup menu item list – Sanyo SANUPS E11A202U User Manual

Page 26

Advertising
background image

− 23 −

10. User Settings

10.1 Setup Menu Item List

You can configure the UPS by setting the menu items in the following list.

Configure it according to your environment and requirements.

The controls and indicators on the control panel are used to set items in the Setup
menu. For details, see §10.2 “Setup Menu Operations”.

Whenever you change a menu item setting, we recommend that you place a check

mark in the “Current Setting” field of the Setup Menu Item List.

No. Menu Item

Item Selection

LEDs

Setting

Item Setting

LEDs

Default

Setting

Current

Setting

Description

Notes

Auto

● ○ ○ ○

*

Switch the UPS operating mode automatically.

Double Conversion ○ ● ○ ○

Set the UPS operating mode to Double Conversion mode.

UPS operation mode

● ○ ○ ○

Economy

● ● ○ ○

Set the UPS operating mode to Economy mode.

However, the mode of UPS might change into the “Double Conversion”

mode depending on the condition of the input potential and the load.

100V

● ○ ○ ○

100V setting

110V

○ ● ○ ○

110V setting

115V

● ● ○ ○

115V setting

Output voltage

(RESTART)

○ ● ○ ○

120V

○ ○ ● ○

*

120V setting

Set the rated output voltage.

The case of E11A202U001

Please do not change setting the voltage.

And use UPS as 120V setting.

(For UL rules)

1%

● ○ ○ ○

±1% allowance

3%

○ ● ○ ○

*

±3% allowance

Frequency sync range
(RESTART)

● ● ○ ○

5%

● ● ○ ○

±5% allowance

Set the range (%) over which the output

frequency is adjusted to variations in the
input frequency in Economy Mode and

Active Filter Mode.

50Hz

● ○ ○ ○

50Hz setting

Battery startup

frequency

○ ○ ● ○

60Hz

○ ● ○ ○

*

60Hz setting

Set the inverter output frequency when

UPS restarts from the batteries from

stopped status.

Do not use this setting.

● ○ ○ ○

Workstation

○ ● ○ ○

*

Setting for communications by the power management software over serial

or LAN connection.

Serial Login

● ● ○ ○

Shutdown by serial login.

PC Interface mode

● ○ ● ○

Do not use this setting.

○ ○ ● ○

9600

● ○ ○ ○

*

Set the baud rate to 9600 bps.

4800

○ ● ○ ○

Set the baud rate to 4800 bps.

Serial baud rate

○ ● ● ○

2400

● ● ○ ○

Set the baud rate to 2400 bps.

Set the communications baud rate when

a workstation, PC, or optional LAN card

is connected.

Auto

● ○ ○ ○

*

Auto restart

OFF

○ ● ○ ○

The UPS stays off.

30%

● ● ○ ○

Same behavior as Auto when

battery charge reaches 30%.

50%

○ ○ ● ○

Same behavior as Auto when

battery charge reaches 50%.

Restart time

(battery charge rate)

● ● ● ○

80%

● ○ ● ○

Same behavior as Auto when

battery charge reaches 80%.

Specify when to restart the UPS after a

power outage and shutdown of the UPS

due to final discharge of the batteries.

When 30%, 50%, or 80% is selected, the
UPS does not restart until the batteries

are charged to the specified level.

All patterns

● ○ ○ ○

*

All sounds

Patterns 1

○ ● ○ ○

Do not emit sounds on power outage, battery test, and overload.

Pattern 2

● ● ○ ○

Emit alarm and key click sounds.

Buzzer sound

○ ○ ○ ●

OFF

○ ○ ● ○

Emit key click sounds only.

1 second

● ○ ○ ○

*

Turn inverter off when pressed for 1 second.

3 seconds

○ ● ○ ○

Turn inverter off when pressed for 3 seconds.

Set the response time for

switch press to stop inverter
power supply.

switch

response time

● ○ ○ ●

Special operation

● ● ○ ○

Turn inverter off on special operation. Select this setting to keep the

inverter from being turned off by an accidental operation. See §9.4 "UPS

Shutdown (Daily)" for operation details.

Auto return

● ○ ○ ○

*

Auto recovery with time

Overload recovery

operation

○ ● ○ ●

Bypass

○ ● ○ ○

Fixed as bypass on overload

Set the conditions for automatic switch

back to inverter power supply (auto

return) after switching to bypass power
supply because of overload.

OFF

● ○ ○ ○

*

The UPS stays off.

Inverter stop

Operation (RESTART)

● ● ○ ●

Bypass

○ ● ○ ○

Switch to bypass operation when

inverter stops.

Specify the UPS operation during

inverter power supply stops.

Battery voltage level

● ○ ○ ○

*

When low battery voltage level is

detected.

2 minutes

○ ● ○ ○

When remaining battery capacity

is 2 minutes.

Low battery voltage

signal timing

○ ○ ● ●

3 minutes

● ● ○ ○

When remaining battery capacity
is 3 minutes.

Specify the timing for triggering the low

battery voltage signal.

5 minutes

● ○ ○ ○

*

5 minutes backup

20 minutes

○ ● ○ ○

20 minutes backup

30

minutes

● ● ○ ○

30

minutes backup

40

minutes

○ ○ ● ○

40

minutes backup

60

minutes

● ○ ● ○

60

minutes backup

90

minutes

○ ● ● ○

90

minutes backup

120

minutes

● ● ● ○

120

minutes backup

Battery backup time

(RESTART)

● ○ ● ●

180

minutes

○ ○ ○ ●

180

minutes backup

Set the UPS backup time on power

outage.

An external battery must be connected

for settings of 20 minutes or higher.

These external battery accommodate by

Technical Service Personnel.Ask for

Tehnical Service Personnel.

Do not use another setting.

5 year

● ○ ○ ○

*

5-year lifetime type

10 year

○ ● ○ ○

10-year lifetime type

Battery type

(RESTART)

○ ● ● ●

3 year

● ● ○ ○

3-year lifetime type

Set the battery type.

Set this when you exchange the battery

or connect an external battery.

180 days

● ○ ○ ○

*

Check batteries every 180 days.

90 days

○ ● ○ ○

Check batteries every 90 days.

30 days

● ● ○ ○

Check batteries every 30 days.

Battery check schedule

● ● ● ●

None

○ ○ ● ○

No battery check.

Set the interval (number of days) for the

automatic battery check. The check is

carried out automatically when the

specified number of days has elapsed.

Do not reset

● ○ ○ ○

*

Do not reset.

Reset remaining

battery life

○ ○ ○ ○

Reset

○ ● ○ ○

Reset the battery information (remaining life, accumulated battery

operating time, number of power outages, LED remaining life display),

when you exchange the battery.

LED blinks

LED off