15.4 Specifications

Item

Standard or Performance

Notes

MODEL E11A202U001

E11A202U001J

(*6)

Output capacity

2.0kVA/1.4kW

Cooling system

Forced air cooling

Type of Input pulg

NEMA 5-20P

NEMA L5-30P

(*6) When the plug is NEMA_5-20, the

input and output voltage of UPS are

120V. only (For UL rules.)

Phases

Single phase, 2-wire

120V 100,110,115,120V

Voltage

-20% to +15% Double Conversion mode

±5% Economy /Active Filter mode

±10% Fixed Economy mode

User settable

(Rated voltage same as output voltage)

Frequency

50Hz or 60Hz

±10%: Double Conversion mode

±1, 3, 5%: Economy /Active Filter mode

Power requirements

1.8kVA

Max. capacity during battery charging

AC in

pu

t

Input power factor

0.95 or more

During rated output (*2)

Type of receptacle

NEMA 5-20R×4 NEMA

L5-30R×1

Phases

Single phase, 2-wire

Voltage

120V

100, 110, 115, 120V (*6) User settable

Voltage regulation

Rated voltage

±2%

Rated frequency

50Hz or 60Hz

Same as input frequency

(auto selection)

Frequency regulation

Rated frequency

±0.5% Double Conversion mode

Rated frequency

±1, 3, 5% Economy/Active Filter

mode

1, 3, 5% selectable
Internal oscillator accuracy

±0.5%

Voltage waveform

Sine wave

Distortion factor of voltage

waveform

Linear load: 3% or less

100% rectifier load: 7% or less

During rated output

Rapid load

change

0%

⇔ 100% at transient or output

switch

Power outage,

recovery

Rated voltage

±5 %

During rated output

Transient

voltage

variation

Rapid input

voltage change

±10% variation

Response time

5 cycles or less

Load power factor (lag)

0.7 (lag)

Variation range 0.7 (lag) to 1.0

Overcurrent protection

Auto switch to bypass circuit at 105% or more With auto return function

Inverter 105%

200ms

AC Ou

tpu
t

Overload

capability

Bypass 20A

or

more

Type

Small sealed lead battery

Rated capacity

10 A・h

20 hour ratio

Number

4 (12V per battery)

4 in direct series

Batte

rie

s

Backup time

5 minutes

At 25°C (77°F) ambient temperature,

rated load

Generated heat

250W

During Double Conversion mode

Input leakage current

3mA or less

Operating environment

Ambient temperature: 0 to 40°C (32 to 104°F)

Relative humidity: 20 to 90%

(*3)

Acoustic noise

45 dB or less

1 m (approx. 40 inches) from UPS front

panel, 'A' characteristics (linear load)

Safety standard

UL1778-4th/C22.2 No.107.3-05-2nd:2005

EMI standard

FCC Part 15,Sub partB,Class-A

And EN55022 Class-A

Other quotation standards

EN62040-1-1:2003 (For LVD)

EN50091-2:1995 (For EMC)

EN55024:1998/A1:2001/A2:2003 (For EMC)

EN55022:1994/A1:1995/A2:1997 (For EMC)

(*1): The inverter is capable of operation synchronized with AC input and instantaneous switchover

provided that the AC input frequency is within

±3% (or 1%, 3%, 5%, selectable) of the rated

frequency, and the AC input voltage is within +15% to-20% of the rated voltage.

The UPS enters battery operation with the AC input frequency is outside the specified range.

(*2): When input voltage waveform distortion is under 1%.

(*3): The UPS contains batteries. Battery service life will be foreshortened if the UPS is used in an

environment where the ambient temperature exceeds 30°C (86°F).

(*4): If grounded, the ground phase of the input and output must match according to UPS specifications.

*****continues to the following page.*****