11.6 Battery Exchange

You can exchange the batteries without stopping the load devices. However, this should be
done as quickly as possible, because the UPS will be unable to provide backup power in the
event of a power outage.

When exchanging the batteries,replace the all batteries.

CAUTION

The battery pack weighs about 12kg (26.46 lbs). Be careful not to drop it on
your feet. Bodily injury can result.

Wear insulated gloves and take other precautions when exchanging the
batteries. Otherwise electric shock can result.

There is a constant voltage (max. approx. 48V: approx. 12V

× 4) at the

battery terminals. Do not touch them with your hands or short circuit them.
Bodily injury can result.

Remove the front panel of the UPS.

Remove the screw on the right side of the battery cover, and then remove the battery

cover.

Disconnect the battery connector.

Pull the battery pack out.















Insert the new battery pack so that the connector faces forward.

Connect the battery connector.



CAUTION

The battery connector cannot be inserted in
the wrong orientation. If it does not go in, do

not try to force it. Doing so can damage the

connector and result in electric shock.

Be careful not to get your hands caught when
securing the cover.

Remove by sliding in the direction

of the arrow while firmly pressing

the two locations indicated by ●

Battery connector. Insulate with

tape or other insulator.

Insert the battery pack

in the direction of the

arrow.

Remove 1 screw, and remove the

battery cover by sliding in the

direction of the arrow.

Do not lose the removed screw.

The connector cannot be

inserted in the wrong

orientation. Push in until

you hear a click.