Siemens SQM5 User Manual

Page 23

Advertising
background image

SQM5… Reversing Actuators

Technical Instructions

Document No. 155-517P25

July 9, 2007

Siemens Building Technologies, Inc.

Page 23

AGA56.9A…
Circuit Board
Installation, Continued

4. Guide the base circuit board from the

switch housing side of the actuator into
the bottom of the circuit board mounting
bracket. See Figure 23.

5. Re-install the actuator motor capacitor.

See Figure 24.

6. Gently guide the terminal board into the

support slots and slide the terminal
board downward until both supports
snap into place. See Figure 25.

7. See Figure 26 and make the following

connections to the actuator:

a. Connect the wire, marked “1” from

the circuit board to switch I,
terminal 1.

b. Connect the wire, marked “2” from

the circuit board to switch II,
terminal 2. Connect the white wire,
marked “3” from the circuit board to
switch III, terminal 3.

c. Connect the wire, marked “13” from

the circuit board to switch III,
terminal 13.

d. Connect the neutral wire, marked

“N” to the double terminal block
located on the outer end of the
switch housing.

e. Connect the grounding wire marked

"51" to the ground terminal located
to the right of the auto/manual
switch.

BASE

CIRCUIT

BOARD

EA0571R1

Figure 23.

EA0572R1

CAPACITOR

Figure 24.

EA0573R1

TERMINAL

SECTION

Figure 25.