Installation and operation instructions – Siemens SQM5 User Manual

Page 7

Advertising
background image

SQM5… Reversing Actuators

Technical Instructions

Document No. 155-517P25

July 9, 2007

Siemens Building Technologies, Inc.

Page 7

Installation and
Operation
Instructions

SQM5… actuators are sometimes shipped without the shaft installed. To install the
selected shaft:

1. Loosen the two screws on the actuator cover corners. See Figure 2.

2. Lift the screws and raise the cover. See Figure 3.

Shaft Installation

EA0564R1

Figure 2.

EA0568R1

Figure 3.

3. Each shaft is supplied with two washers and a “C” clip. See Figure 4. Using

spreading pliers, remove the “C” clip and the washers from the shaft.

WASHERS ON

BOTH SIDES

OF THE BEARING

SHAFT KEY

EA0559R1

C-CLIP

INSERT END

KEY END

Figure 4.

4. Insert the “insert end” of the shaft into the “gear end” of the actuator.

5. Push the shaft until the “insert end” reaches just short of the brass bushing at the

other end of the actuator.

6. Put one of the washers on the insert end of the shaft. See Figure 5.

WASHERS

EA0569R1

Figure 5.

7. Line up the “shaft key” with the key slot on the “gear end” of the actuator and slide

the shaft until the “insert end” is completely through the brass bushing.

8. Place the second washer onto the “insert end” of the shaft. Using spreading pliers,

install the “C” clip.

Advertising