Troubleshooting the millivolt control system – Superior SDVST-N-B User Manual

Page 22

Advertising
background image

22

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

1. Spark igniter will not light pilot after

repeated triggering of igniter button.

WARNING: if the pilot will not light

after 1 minute of attempting, wait
for at least 5 minutes for gas to
clear before attempting again.

A. Defective igniter
(no spark at electrode).

Check for spark at electrode and pilot; if no spark
and electrode wire is properly connected, replace
igniter.

B. Defective or misaligned electrode at pilot

(spark at electrode).

Using a match, light pilot. If pilot lights, turn off pilot
and trigger the igniter button again. If pilot lights, an
improper gas mixture caused the bad lighting and a
longer purge period is recommended. If pilot will not
light – check gap at electrode and pilot – should be
1/8" to have a strong spark. If gap does not measure
1/8", replace pilot (see Figure 11 on Page 14).

C. Gas supply pressure errant.

Check inlet gas pressure. It should be within the limits
as marked on the rating plate.

D. Pilot orifice plugged.

Clean or replace pilot orifice.

2. Pilot will not stay lit after

carefully following the lighting
instructions.

A. Defective pilot generator
(thermocouple).

Check pilot flame, it must impinge on thermocouple
(see Figure 11 on Page 14). Clean and/or adjust pilot
for maximum flame impingement on thermocouple.
Ensure that the connection between the valve and
thermocouple are tight and secure.

3. Pilot burning, no gas to burner, Valve

knob “ON,” (and *optional remote
switch, if applicable) is “ON." Read
important note below.

IMPORTANT NOTE: If an optional

*remote switch is used for burner

operation, the unit-mounted burner

OFF/ON switch (if installed) must be

in the "OFF" position.

*Optional remote switch kits - wall

switch, wall thermostat or remote

control.

A. *Optional remote switch or wires defective. Check *remote switch and wires for proper connec-

tions. Jumper wire across terminals at switch, if burner
comes on, replace defective switch. If okay, jumper
wires across switch wires at valve, if burner comes
on, wires are faulty or connections are bad.

B. Thermopile may not be generating suf-

ficient millivolts.

Check thermopile with millivolt meter. Take reading at
thermopile terminals of gas valve. Should read 325
millivolts minimum with *optional remote switch
“OFF.” Replace faulty thermopile if reading is below
specified minimum.

C. Plugged burner orifice.

Check burner orifice for blockage and remove.

4. Frequent pilot/burner outage prob-

lem.

A. Pilot flame may be too low or blowing

(high) causing the pilot/valve safety to drop
out.

Clean and/or adjust pilot flame for maximum flame
impingement on thermocouple (see Figure 11 on
Page 14)
.

TROUBLESHOOTING THE MILLIVOLT CONTROL SYSTEM

Note: Before troubleshooting the gas control system, Ensure external gas shut off valve, located at gas supply inlet, (and

wall switch, iff applicable), is in the “ON” position.

Important: Valve system troubleshooting should only be accomplished by a qualified service technician.

Advertising
This manual is related to the following products: