Chapter 4 — Programming Considerations

13,29,45,61

24
25

14,30,46,62

26
27

15,31,47,63

28
29

16,32,48,64

30
31

1560-MBP

Modbus Plus

Address

Global Data

Table

Index

Description

Control Word
Reference Word
Control Word
Reference Word
Control Word
Reference Word
Control Word
Reference Word

This instruction “publishes” Global Data on the Modbus Plus network
from the Host PLC. Up to 32 words can be transmitted from the Host,
allowing up to 16 1560-MBP units to be controlled. When the 1560-MBP
reads the Global Data it first examines the source node address to
assure it matches the dip switch configured Host Node Address, and
then retrieves the two words that relate to its node from the packet.

enable -

abort -

Modicon Programming Example - MSTR 5

- active

40400

40410

MSTR
00032

- error

- success

Contents of registers in control block

40400 = 5 Global write data instruction
40401 = 0 Error code
40402 = 32 Global Data block length
(Max 32 words)
40403 = 0 N/A
40404 = 0 N/A
40410 = Source of the Global Out Data