A - left a - right, Long shaft short shaft – Schneider Electric DuraDrive Direct Coupled Actuators MA4X-707X User Manual

Page 13

Advertising
background image

F-26642-8

© Copyright 2010 Schneider Electric All Rights Reserved.

13

B

Shaft Rotates

Clockwise

To Open

Shaft Rotates

Counterclockwise

To Open

A - Left

A - Right

This step determines
shaft rotation. Linkage
may change damper direction.

For MA41-707X and MA41-715X only (manual override).
For MA40-707X and MA40-715X, proceed to step C.

R

R

L

LO

CK

R

L

LOCK

If position indicator does not point to zero:Unlock the actuator.

Insert hex wrench into manual override.
Crank the actuator so the indicator points to

.

Lock the actuator.

Caution: Do not crank the manual

override if power is applied
to the actuator.

Manual Override

Unlock

Long Shaft

Short Shaft

Min. 3 1/2" (90 mm)

3/8" to 3/4" Diameter (10 mm to 20 mm)
3/8" to 1/2" Square (10 mm to 13 mm)

Min. 3/4" (20 mm)

Move the damper to its normal position. Verify the controller action is set to match the
damper application.

Normally closed damper: when damper is closed, actuator position indicator should
be at 0°. When damper is open, actuator position indicator should be at 90°.

Normally opened damper: when damper is open, actuator position indicator should
be at 0°. When damper is closed actuator position indicator should be at 90°.

Fully engage hex wrench
into manual override before
winding.