INSTALLATION

Inspection

Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If
undamaged, open the package and inspect the device for obvious damage. Return
damaged products.

Requirements

Job wiring diagrams

Tools (not provided):

– #8 sheet metal screws
– 10mm open end wrench or socket wrench
– 7/16 inch, open end wrench or socket wrench
– 1/8 inch, allen wrench
– Appropriate screwdriver(s)

Appropriate accessories

Training: Installer must be a qualified, experienced technician

MA40-7040
MA40-7041

MA40-7040-501
MA40-7041-501

120 Vac or

230 Vac

Wire No. 1

Wire No. 2

Neutral

Hot

2

2

Wire No. 2

Wire No. 1 Neutral

Hot

L1 N
L2 H

L1 N

L2 H

1

1

3

Orange

Violet

Yellow

N.C.

COM.

N.O.

Auxiliary Switch 1

1 Provide overload protection and disconnect as

required.

2 Actuators may be wired in parallel. Power

consumption must be observed.

3 For end position indication, interlock control, fan

startup, etc., MA40-704X-501 model incorporates
one built-in auxiliary switch. See Specifications
section for details.

120 Vac or

230 Vac

Green/Yellow

Green/Yellow

Voltage

Wire 1

Wire 2

120 Vac

White

Black

230 Vac

Light Blue

Brown

0 to 1 Scale

Adjustable

Figure-2 Typical Wiring Diagram for 120 Vac or 230 Vac Basic and Single Auxiliary Switch Models.

MA40-7043

MA40-7043-501

24 Vac

2

2

Red

Black

Common

Hot

1

1

(1)

(2)

3

Orange

Violet

Yellow

N.C.

N.O.

Auxiliary Switch 1

Line

Volts

1 Provide overload protection and disconnect as

required.

2 Actuators may be wired in parallel. Power

consumption must be observed. Actuator may also
be powered by 24 Vdc.

3 For end position indication, interlock control, fan

startup, etc., MA40-7043-501 model incorporates
one built-in auxiliary switch. See Specifications
section for details.

24 Vac

Black

Red

Common

Hot

Line

Volts

SPST Control Contact

SPST Control Contact

Green/Yellow

Green/Yellow

0 to 1 Scale

Adjustable

Figure-3 Typical Wiring Diagram for 24 Vac Basic and Single Auxiliary Switch Models.